Owner`s manual

Page 16
Controls must be far enough from the gate so that the user is prevented from coming in
contact with the gate while operating the controls. Outdoor or easily accessible controls
should have a security feature to prevent unauthorized use.
Connect optional control devices to the master operator terminal strip as shown in Figure 25.
Be sure that all electrical connections are made in accordance with local electrical codes.
Use 18 AWG wire for all low voltage wiring, maximum distance 3000 feet. Use a low voltage
surge suppresser, DoorKing P/N 1878-010 if low voltage wire runs exceed 1000 feet. All
inputs to the terminal strip must be NORMALLY OPEN.
Standard reversing input (term 15) only functions while the gate is in the closing cycle and
should not be used as an input for a secondary entrapment protection device for the open
gate cycle. See section 2.2.2 for secondary entrapment protection device wiring.
Do not power any devices from the circuit board other than a low voltage radio receiver.
Three-button control station must be DoorKing P/N 1200-006 only. Others will not work.
If magnetic lock is used, refer to section 2.4.