Owner`s manual

9510-065-L-3-13
18
3.2 DIP-Switch SW 1 and SW 2 Settings
The two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn on
or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then
turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.
Switch Function Setting Description
SW 2 - Left 4 Switches
2
Spare
4
Warn Before
Operate
1
Reverses Gate
Stops Gate
Switch Function Setting Description
SW 1 - Right 8 Switches
OFF
ON
4-OFF
4-OFF
4-ON
4-ON
5-OFF
5-ON
5-OFF
5-ON
Auto-Close
Timer
Relay Activation
and
LED Indicator
Light Activation
2
1
3
4 and 5
7
8
OFF
ON
OFF
ON
Normal Setting. No sound.
Internal alarm will sound before gate starts and throughout gate’s cycle.
Auto-close timer is OFF. Manual input required to close gate.
Auto-close timer is ON. Adjustable from 1-23 seconds to close gate.
Self-Test
Gate Opens
Uphill
3
Gate Opens
Downhill
6
Relay activates and LED is ON when the gate is fully open.
Relay activates and LED is ON when the gate is not closed.
Relay activates and LED is ON when the gate is opening and open.
Relay activates and LED is ON when the gate is opening and closing.
Changes the direction the operator
will open/close the gate.
Opening direction
using ON setting.
Opening direction
using OFF setting.
Normal Setting. Input to terminal #6 and/or reverse loops will REVERSE gate
during CLOSE cycle.
Input to terminal #6 and/or reverse loops will STOP gate during CLOSE cycle.
OFF
ON
OFF
ON
Normal Setting. Normal gate operation.
Self-test mode. Operator MUST be disconnected from gate to run self-test.
OFF
ON
Normal Setting. Level gate operation or gate opens DOWNHILL.
MUST be ON if gate opens UPHILL.
OFF
ON
Normal Setting. Level gate operation or gate opens UPHILL.
MUST be ON if gate opens DOWNHILL.
OFF
Leave in the OFF position.
Exit Loop Port
Output
Full Open Input
The output wired to terminal #4 becomes the output from the exit loop detector
plugged into the EXIT Loop port. Used for dual operator application.
Normal Setting. Terminal #4 is a normal full open input.
OFF
ON
1
ON
2 3 4 5 6 7 8 1
ON
2 3 4
Typical
Settings
Left 4 Switches - SW 2
SW 2 is Upside-Down on Circuit Board.
SW 1 - Right 8 Switches
SW 1 is Upside-Down on Circuit Board.
Normal Setting. Timer will function normally.
Opening gate will stop and begin to close as soon as all reversing inputs (Reverse
loops, photo sensors) are cleared regardless of the distance the gate has opened.
Quick-Close
Timer Override