Manual B-Net® 91 04 Mounting and Installation
12/2008 © Kaba GmbH 23
5.9 DIP-Switch
The DIP switch row is located under the lower front panel. Therefore, the switches
must be adjusted before fixing the front panel.
Remark
All switches are set to ON when delivered.
1
OFF
234
5678910
Fig. 10: DIP switch position
GID/DID
The group and device identifications (GID/DID) serve for addressing a subterminal
via the RS-485 interface. This setting is required if the device is used as a
subterminal in an access control unit.
Switch 1 2 3 4 Logical device address (DID)
on on on on 00
off on on on 01
on off on on 01
off off on on 03
on on off on 04
off on off on 05
on off off on 06
off off off on 07
on on on off 08
off on on off 09
on off on off 10
off off on off 11
on on off off 12
off on off off 13
on off off off 14
off off off off 15
Switch 5 6 7 Logical group address (GID)
on on on 00
off on on 01
on off on 01
off off on 03
on on off 04
off on off 05
on off off 06
off off off 07