Start-Up Manual B-Net® 91 04
28 © Kaba GmbH 12/2008
6.1 Stand-alone operation
Requirements
The connections to power supply and door opener must exist.
The DIP switches must have been set in accordance with the description in
chapter
5.9.
A service PC and the parameter setting tool, order number 04036126, must
be available. In the service PC, the program "List Editor" (listedit.exe) must
have been installed. This program is part of the parameter setting tool.
Set-up procedure
1. Connect the service PC via the parameter setting tool to the B-Net 91 04.
Use the yellow connecting cable for connecting B-Net 91 04 to the
parameter setting tool.
RS-232C
RS-485
B-Net 91 04
Para-Tool
Service-PC
Fig. 12: Connecting the service PC to B-Net 91 04
2. Provide the parameter setting tool with power (B-Net 91 04 is also supplied
with power).
3. Start the "List Editor" on the service PC.
In the Options menu, the COM port must have been selected and the device
address used of the B-Net 91 04 must have been set.
4. Prepare the desired customer number list and load it to the subterminal.
If a list entry contains 14 digits of customer and badge number in
accordance with the Kaba group header, a single badge will be authorized.
If a list entry contains, for example, only an 8-digit customer number in
accordance with the Kaba group header, a badge group will be authorized.
5. Activate the stand-alone operation and enter the relay pull-in time (default 3
seconds).
6. Perform a functional test.
7. Service PC and parameter setting tool are no longer required and can be
removed.
Remark
The operation of the List Editor is described in the manual of the parameter setting
tool.
The description of the customer number list can be found in chapter
8.7.8.