User's Manual

Table Of Contents
Installation Technical Manual
44 - 06/2016 Kaba Remote Reader 91 15-AM (US/
CAN)
Item Connection/switch Remark
9 Power supply 12–27VAC (50/60Hz) or 10–34VDC
Notice: The device may only be supplied with SELV (Safety Extra Low
Voltage) and LPS (Limited Power Source), according to IEC/UL/CSA
60950-1.
See also: Using several remote readers [}5.3.2.3]
Set RS-485 termination resistances [}5.6.3]
5.5.2 Inputs IN1–IN2
NOTICE
Connecting Isolated Inputs.
The function of the inputs and outputs depends on the control unit used and its pa-
rameter settings.
The logic (normally open [active low]/normally closed [active high]) of the inputs can
be changed by the host system.
Allocation Meaning
GND (common ground)
IN1
(input 1)
Door handle contact or door opener key REX
IN2
(input 2)
Frame contact (FC)
If the Kaba Remote Reader 91 15 needs to behave in the same way in both online and
offline operation, the inputs and relay outputs must be connected according to the
operating mode and configured with the DIP switches.
DIP switches 3 and 4 define the function of inputs IN1 and IN2.
DIP Switch
IN1 and IN2 can, when necessary, be used as line-monitored inputs.
Inputs IN1–IN2 With Line Monitoring [}5.5.2.2]