5.6.3 Set RS-485 termination resistances
The connection architecture determines the terminating resistors.
1. Set terminating resistors in accordance with the following description.
Star wiring
4
,7
kΩ4
,7
kΩ4
,7
kΩ 4
,7
kΩ4
,7
kΩ
120 Ω
RS-485
2
1
3
1 Host control device (Kaba access manager AM)
2 Distributor (e.g. screw terminal)
3 Terminating resistors Kaba Remote Reader 91 15
1. Set the terminating resistor to 4.7kΩ on all Kaba Remote Reader 91 15 (3).
DIP switch number Position Effect
1 ON Terminating resistance 4.7kOhm (star wiring)
2 OFF open
1. Set the terminating resistor to 120Ω on the host control system (1).
Bus wiring with 1 bus
120ΩOPENOPENOPENOPEN
RS-485
120 Ω
1
2
3
3
1 Host control device (Kaba access manager AM)
2 Kaba Remote Reader 91 15
3 Terminating resistors
1. Set the terminating resistor to 120Ω on the last Kaba Remote Reader 91 15 of the
bus wiring.
DIP switch number Position Effect
1 ON Terminating resistance 120Ohm
2 OFF open