5.2 Installation lines
5.2.1 24 V DC power supply
A 3-wire cable is required for supplying power to the terminal
(+24 V/0 V/ground wire).
The housing of the terminal must be connected to earth. Therefore, the ground wire must be
carried from the power supply to the terminal.
The terminal is designed for the following max. wire sizes:
Diameter (Ø): 2.7 mm
Cross-section: 2.5 mm
2
AWG number: 12
In case of long lines, the voltage drop due to line resistance will have to be taken into account.
5.2.2 Mains voltage supply
A 3-wire cable is required for the mains voltage supply (phase/zero/protective conductor).
The terminal is designed for the following max. wire sizes:
Diameter (Ø): 2.7 mm
Cross-section: 2.5 mm
2
AWG number: 12
5.2.3 Ethernet
Network cable with RJ45 plug, line requirement: CAT.5 S-UTP 4 x 2 AWG 24 oder AWG 22 (ac-
cording to EIA/TIA568) or higher quality.
5.2.4 Inputs/Outputs
The terminals for the signal lines are designed for the following max. wire sizes:
Diameter (Ø): 0.3 – 1.4 mm
Cross-section: 0.08 – 1 mm
2
AWG number: 28 - 16
Recommended cable:
CAT.5 S-UTP 4 x 2 AWG 24 or AWG 22 (according to EIA/TIA568) or higher.