2904047408 - 10/2020 dormakaba access manager 92 009200-K7 TP4-Client
5.2 Installation lines
5.2.1 General requirements
The installation of the cables must conform to the current national and local regulations. In
general, the following requirements apply.
Protection against manipulation
Install the cables inside the security areas.
Install the cables so that they are hidden or difficult to access.
Avoiding malfunctions
Keep the cable routes short.
Lay low-voltage and data lines away from sources of interference.
5.2.2 Ethernet
Network cable with RJ45 plug, line requirement: CAT.5 S-UTP 4 x 2 AWG 24 oder AWG 22 (ac-
cording to EIA/TIA568) or higher quality.
5.2.3 Lines to RS-485 devices
The RS-485 devices are connected via a bus in 2-wire technology.
Wiring requirements
Shielded line with twisted wire pairs.
No other signals may be carried in the wire, except for the low voltage for the power sup-
ply to the RS-485 devices.
Cable lengths:
Lt The total permissible length (master and branch lines) is max. 1200m.
La If the RS-485 bus and the extra-low voltage is led through one cable, the max. permiss-
ible length is 20m.
If the distance is long, lay a separate line for the low voltage.
Lb Low voltage in a separate cable
The length depends on the voltage drop of the cable.
The voltage must conform to the requirement of the RS-485 device.
For longer distances, use a local power supply.
Ls The permissible length per branch line is max. 100m.
Not recommended, since branch lines can cause malfunctions.