4. FUNCTIONALITY
Functional Capabilities
Each device, when installed in a luminaire with a suitable LED driver having 0-10V dimming, Dim-to-OFF capability and an auxiliary
power output, performs the following functions:
LED status indicator for network status and commissioning. For the Intelligent Fixture Sensor, the LED also indicates
occupancy detection events.
ON/OFF control, using the DIM-to-OFF feature of a suitably equipped LED driver
UP/DOWN dimming control
On-board Reset (press bezel and hold for 10 seconds)
Intelligent Fixture Sensor provides:
Occupancy Control modes (see table below)
Primary and Secondary Daylight Harvesting (CLC)
Out-of-Box Functionality
Intelligent Fixture Sensor:
Occupancy mode (Auto ON/Auto OFF)
Timeout: 20 minutes
Local occupancy (independent of other sensors)
100% Max output level on both output channels
Intelligent Fixture Controller:
Once it is fully powered, the BT-IFC-A will go to 100%.
Power-up Sequences for Non-Networked Devices
Intelligent Fixture Sensor & Intelligent Fixture Controller:
When initially powered up or if power is cycled, the unassociated sensor will initiate the following start sequence:
1. 3 seconds OFF
2. 6 seconds at 100%
3. 3 seconds OFF
4. 3 seconds at 30%
5. Transition to 100%
*LED will rapidly blink GREEN to indicate unassociated devices
When occupancy is detected When time-out occurs
Occupancy
Auto ON Auto OFF
Vacancy
Manual ON required Auto OFF
Partial ON
Auto ON to 50%
Manual ON to 100% required
Auto OFF
Partial OFF
Auto ON to Zone MAX Transition to Zone MAX