Operating Instructions and Installation Instructions

The flue or chimney must be made of fire-resistant
material, preferably ceramics or stainless steel.
The flue or chimney must be airtight and well-
cleaned and guarantee sufficient draught.
A draught/vacuum of 15-20Pa during normal
operation is ideal.
Starting from the flue spigot, the flue must run as
vertically as possible. Changes in direction and
horizontal pieces disrupt the outward flow of com-
bustion gases and may cause soot deposits.
To prevent combustion gases from cooling down
too much, which reduces the draught, ensure that
the interior diameter is not too big.
The flue or chimney should ideally have the same
diameter as the connection collar.
For the nominal diameter: see the appendix
"Technical data". If the smoke channel is well
insulated, the diameter may be slightly bigger
(up to 2x the section of the connection collar).
The section (area ) of the smoke channel must be
constant. Wider segments and (in particular) nar-
rower segments disrupt the outward flow of com-
bustion gases.
When using a cover plate or exhaust hood : make
sure that the cover does not restrict the flue outlet
and that the cap does not impede the outward flow
of combustion gases.
The flue must end in a zone that is not affected by
surrounding buildings, trees or other obstacles.
The flue outside the house must be insulated.
The chimney must be at least 4metres high.
As a rule of thumb: 60cm above the ridge of the
roof.
If the ridge of the roof is more than 3metres away
from the flue: stick to the measurements in the fol-
lowing figure. A = the highest point of the roof
within a distance of 3metres.
Ventilation of the area
For good combustion, the stove needs air (oxygen).
This air is supplied via adjustable air inlets from the
area in which the stove is installed.
The combustion will be incomplete in case of
insufficient ventilation, which results in toxic
gases being produced and spread through the
area.
As a rule of thumb, the air supply should be
5,5cm²/kW. Extra ventilation is needed when:
The stove is in an area that is well-insulated.
There is mechanical ventilation, for example a cent-
ral extraction system or an extraction hood in an
open kitchen.
You can provide extra ventilation by having a vent-
ilation louvre fitted on the outside wall.
Make sure that other air consuming appliances (such
as tumble-driers, other heating appliances or a bath-
room fan) have their own supply of outside air, or are
switched off when you use the appliance.
You can also connect the appliance to an out-
side air supply. A connection kit is supplied for
this purpose. This makes additional ventilation
unnecessary.
Floors and walls
The floor on which the appliance is placed must have
sufficient bearing capacity. For the weight of the appli-
ance, see the appendix "Technical data".
Protect flammable flooring from heat radiation
by means of a fireproof protective plate. See
Subject to change because of technical improvements
7