User`s guide

B-10
Parameter Settings in Each Monitoring Mode, continued
Setup
parameters
(continued)
The following table lists the default settings for the threshold parameters in each
monitoring mode.
*Numbers are in percent of nominal unless otherwise specified.
Parameters
Standard Power
Quality
Long-term
Timed Recording
Continuous Data
Logging
EN50160
Waveform Capture Trigger Response
When Volts
go out,
record:
All Active
Channels
Off Off All Active
Channels
When Amps
go out,
record:
Fault Amps
Channels
Off Off Fault Amps
Channels
Journal Intervals
Volts 10 minutes 10 minutes 1 second 10 minutes
Amps 10 minutes 10 minutes 1 second 10 minutes
Power 10 minutes 10 minutes 1 second 10 minutes
Demand 15 minutes 15 minutes Off 15 minutes
Energy 10 minutes 10 minutes Off 10 minutes
Harmonics 10 minutes 10 minutes Off 10 minutes
Flicker (Pst) 10 minutes 10 minutes Off 10 minutes
Flicker (Plt) 2 hours 2 hours Off 2 hours
Characterizer
Mode
IEEE 1159 IEEE 1159 None IEC
61000-4-30