Installation Instructions
Note: If you need to bind a MiStat thermostat, enter the MiStat menu as described in 
Step 4 until 11 WIRELESS is shown, press +/- to show 12 BIND, press ( ) to select. You 
also need to enter the binding process on the MiTime unit, by entering the installer 
menu, then the zone setting and RF binding menu options as shown in the table above.
Technical Data
MiTime T710R, T720R, T740R, T720M, T740M
Voltage  MiTime: 230V a.c. 
MiStat: 2 x AA, 1.5V alkaline batteries 
Switch Rating  MiTime: 2 (1) A 230V a.c. each switch 
Ambient temp  Operating: 0º to 45ºC (MiTime 3/4 
channel 0º to 40ºC, MiStat C 0º to 50ºC) 
Storage: -20ºC to 55ºC 
Without mains 
power 
MiTime Display: blank. MiTime Time: 
always kept. MiTime Programme times: 
always preserved 
Programming 
resolution 
MiTime: 1 minute 
Pollution degree MiTime: 2
Rated impulse 
voltage
MiTime: 2.5kV
Ball pressure test 
temperature
MiTime: 75°C
Radio frequency 868.3 MHz (Bi-directional communication)
Radio signal 
range
30m typically. The range may be 
affected by the composition / density 
and number of walls between the 
MiTime and MiStat
Temperature 
range
MiStat Room: 5°C to 30°C
MiStat Cylinder: 40°C to 70°C
Control accuracy Mistat Room: <0.6°C at 4°/hour
MiStat Cylinder: +0/-8°C
Wiring MiTime: Fixed wiring only, to comply 
with current IEE regulations (BS7671)
MiStat Room: No wiring required
MiStat Cylinder: Ø0.5mm
2
 2 core cable 
between Sensor & MiStat
Mounting MiTime: Industry standard wallplate
MiStat: Wall bracket or table stand
MiStat Sensor: Direct mounting onto 
cylinder
Energy Class IV = 2% (According to EU 811/2013,
812/2013, 813/2013)
Relevant EC 
Directives:
2006/95/EC Low Voltage Directive
2004/108/EC Electromagnetic 
Compatibility Directive
1995/5/EC R&TTE Directive
2006/66/EC Battery Directive
2011/65/EU RoHS Directive
Applied 
Standards:
EN60730-1; EN60730-2-7; EN60730-2-9
ETSI EN 300 220-3; ETSI EN 301 489-3
Step 7: Connection Charts
Step 8: Installer Settings
Feature: Description: Factory Pre-Set:
Min on/off (*only 
when Control type 
is On/of f)
Select 1 min., 3 min., 5 min. or 10 min. 1 min.
Hysteresis (*only 
when Control type 
is On/of f)
Enable or disable Hysteresis Disabled
Frost Protection 
*Heating zones
only
Enable or disable the Frost protection in the 
MiTime unit. 
Disabled
Valve protection The output will be activated for the specifi ed time 
(in minutes). This will happen weekly, related to the 
last actuation of the output. Select 0 to 10 minutes.
0 minutes (Off)
Screen lock Enable or disable the lock in the MiTime unit. 
To Lock: Enter a 3 digit code for protection
To Unlock: Enter the 3 digit code
000
Master Code 401
Powersave To reduce power use when not being adjusted. 
Available options are: Powersave off, partial display 
with key data, no display until button press
Powersave off
System Reset Will reset all settings to factory per-sets 
Signal Strength Informs about the current signal strength in the various zones 
Service Settings To help comply with regulation 36 of the Gas safety [Installation & Use] 
regulations 1998
Si Status Enable or disable Service mode Disabled
Si Type Select between, Reduced Comfort, Switched Off & 
No Effect (warnings only)
Reduced Comfort
Reduced comfort 
duration
Set the duration for the reduced comfort setting 
(0 to 60mins.)
15 min.
Si due date Set the date the next boiler service is due Today
Warning start Set the number of days for the on-screen service 
due warning (0 to 60 days)
30 days
Boost status Enable or disable Service Boost Disabled
No. of boosts Set the number of Boosts to be available after 
service is due (1 to 99)
10
Audible Alarm Enable or disable Service Alarm Enabled
Installer tel Enter the Installer telephone number if required
Set password Set password to restrict access to the Service 
settings
0000
Feature: Description: Factory Pre-Set:
Installer Settings
! CAUTION!  These settings should only be modifi ed by a qualifi ed person. 
They can infl uence safety and the proper functioning of the system.
Zone Settings Customise the MiTime according to personal requirements. These are 
settings which will be applied to a connected room/cylinder stat.
Select zone Select a zone for the following actions
Rename zone To rename an existing zone Heating, H Water,Bed 1
View Product 
Information
View the product details, e.g. Part number, 
Firmware revision etc.
Minimum temp It will not be possible to set a lower temperature 5C (Cyl stat = 40C)
Maximum temp It will not be possible to set a higher temperature 30C (Cyl stat = 70C)
Eco temp. Temperature used for energy saving periods e.g. 
during the night
16C (Cyl stat = N/A)
Comfort temp. Temperature used for comfort periods e.g. during 
the day 
21C (Cyl stat = N/A)
Backlight settings Available options are: On with timeout, Always Off On with timeout
Temp. offset Adjust the displayed temperature to personal needs 0C (Cyl stat = N/A)
Screen lock Enable or disable the lock in the room unit
To Lock: Enter a 3 digit code for protection
To Unlock: Enter the 3 digit code
000
Master Code 401
RF Binding Bind the remote thermostat to the receiver. Pre-bound
Delete zone 
(not T710R)
To delete an existing zone. The last zone cannot 
be deleted
Min. 1 Zone
Add Zone
(not T710R)
Add a new zone, apply a name & bind a thermostat.  
A time table can be applied.
T720: Max. 2 Zones
T740: Max. 4 Zones
System Settings These are the settings which will be applied to the MiTime unit
View product 
information
View the product details, e.g. Part number, 
Firmware revision etc.
Backlight settings Available options are: On with timeout, Always On, 
Always Off
On with timeout
Control type 
*Heating zones
only
Select TPI, TP or On/Off. TPI = Use if the house 
usually reaches setpoint in < 1 hour. TP = Use if the 
house usually reaches setpoint in > 1 hour
On/Off = Use if the boiler should not switch 
regularly, e.g. Solid fuel.
TPI
Cycle rate (*only 
when Control type 
is TPI or TP)
Select 3 cph (cycles per hour), 6 cph or 12 cph 6 cph
! IMPORTANT:
Always switch off the mains before removing 
the MiTime programmer – and never fi t it to a live 
wall-plate!
Arrowed numbers relate to the junction box. 
* Consult boiler handbook for details of pump
overrun wiring.
Make the wiring connections, as above, for the 
appropriate system. For surface wiring, snap out the 
cable entry strip on the bottom edge of the wall-plate. 
MiTime units are double-insulated and need no earth 
connection, but an earthing continuity (loop) terminal is 
provided for convenience.
After wiring, plug in the unit and tighten the securing 
screws. Check the mains input has a 3A fuse, and switch 
on the mains.
Bifl o system: Model T720R
Bifl o system: Model T720M
Twinzone system: Model T720R
3 Zone system: Model T740MTwinzone system: Model T720M
From the Home screen, select 
Settings, then Installer settings 
as shown.
If using the Service feature, 
remember to set the Password 
when complete.
From here you can edit the 
assigned zones, rename them if 
required and adjust the Service 
settings.
 
 
 
3 Zone system: Model T740R