Installation Guide

24
UNIDOOR-X (STYLE M) manual Ver 2 11/2016
2
4
Door
1”
1
2
3
4
5
6
7
8
Around Bottom sweep
measure
measure
1
Handle side of door
Fig 28
Fig 27
3
Panel
22. Measure the bottom of the Door Glass (#01) from
side to side to determine the actual width of the door.
Cut the Bottom Anti-Water Strip (#07) to the size of
your measurement and notch 3/8” of the inner side of the
Bottom Anti-Water Strip (#07) as shown in Fig 27.2.
Press the Bottom Anti-Water Strip (#07) onto the
bottom edge of the Glass Door (#01).
NOTE: Make sure the Bottom Anti-Water Strip (#07) is
flush to the vertical edge of the handle side of the Door
Glass (#01). (Fig 27)
23. To install the Flanged Anti-Water Strip (#33), take three measurements :
• from the top edge of the Door Glass (#01) to the top of the center portion of the top Hinge (#06)
(see Fig 28.1 for an example to use for taking all three measurements)
• from the bottom of the center portion of the top Hinge to the top of the center portion of the
bottom Hinge (#05)
• from the bottom of the center portion of the bottom Hinge (#05) to the threshold
Cut the Flanged Anti-Water Strip (#33) according to these measurements. Notch the cut strips to
slide them into the hinges and around the installed Bottom Anti-Water Strip (#07) to cover the
space between both glass panels. Open the door and press the cut strips onto the vertical edge of
the Door Glass (#01) so they will overlap the panel glass. (Fig. 28)
©2017 DreamLine. All Rights Reserved