Specifications
DRI-STEEM CRUV Electric Humidifier Installation, Operation, and Maintenance Manual • Page 21
Installation
Dispersion:
Rapid-sorb
Table 21-1:
Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb evaporative dispersion units
Airflow
Type of
interconnecting piping
Diameter of
interconnecting piping
Pitch of
interconnecting piping
Pitch of
dispersion tubes
Pitch of
header
Horizontal
Vapor hose
1½" (DN40)
2" (DN50)
2"/ft (15%)
toward Rapid-sorb
Vertically plumb
1/8"/ft (1%)
toward condensate
drain
Tubing or pipe
1½" (DN40)
2" (DN50)
1/8"/ft (1%)
toward Rapid-sorb
Vertical
Vapor hose
1½" (DN40)
2" (DN50)
2"/ft (15%)
toward Rapid-sorb
2"/ft (15%)
toward header
1/8"/ft (1%)
toward condensate
drain
Tubing or pipe
1½" (DN40)
2" (DN50)
1/8"/ft (1%)
toward Rapid-sorb
mc_060310_1000
Table 21-2:
Rapid-sorb dispersion tube capacities
Tube capacity Tube diameter
lbs/hr kg/h inches DN
≤ 35 ≤ 16 1½ 40
36-70 17-32 2 50
mc_060210_0935
Table 21-3:
Rapid-sorb header capacities
Header capacity Header diameter
lbs/hr kg/h inches DN
≤ 250 ≤ 113 2 50
251-500 114-227 3 80
501-800 228-363 4 100
801-1300 364-591 5 125
1301-2100 592-955 6 150
mc_060210_0936
Pitch requirements
• For Rapid-sorb with the header outside a
horizontal-airflow duct, consider the following:
– 1½" (DN40) dispersion tubes: Use a fastener of sufficient
length to accommodate the 1/8"/ft (1%) pitch requirements
toward the ¾" pipe thread (DN20) header drain fitting.
– 2" (DN50) dispersion tubes: The bracket can be mounted
flush to the ductwork. The 1/8"/ft (1%) pitch typically can be
accomplished in the length of the hose cuffs used to connect
the tubes to the header.
• See Table 21-1 and the drawings on the following pages for
pitch requirements.
mc_060210_0953-NA