Page 36 • DRI-STEEM CRUV Electric Humidifier Installation, Operation, and Maintenance Manual
Maintenance
Tap/softened water
Table 36-1:
CRUV torque specifications
Screw or lug location
Torque
in-lbs N-m
Power block 16 1.8
Contactor 16 1.8
Heater
nut
8-32 (8.5 mm) nut 20 2.2
10-32 (9.5 mm) nut 25 2.8
Heater
wire lug
6 gauge (10 mm
2
) wire 35 4.0
8 gauge (6 mm
2
) wire 25 2.8
10-14 gauge (<6 mm
2
) wire 20 2.2
mc_070710_1655-CRUV
Humidifier De-scaling Solution
Scale buildup on humidifier heaters acts as an
insulator, reducing humidifier performance while
increasing energy costs. To keep humidifiers
operating as efficiently as possible, remove scale
with DRI-STEEM's Humidifier De-scaling Solution,
available for purchase from your DRI-STEEM
representative or distributor.
The De-scaling Solution cleans without risk
of corroding humidifier tanks or welds. The
De-scaling Solution also cleans surfaces
unreachable by hand scraping.
DRI-STEEM's Humidifier De-scaling Solution is
the only approved cleaner/de-scaler for use with
DRI-STEEM humidifiers. Use of other cleaners/
de-scalers may void your DRI-STEEM warranty.
PFBB
Install the probe and probe plug assembly. Verify ground
wire is solidly connected to tank.
Secure the chamber cover, making sure the cover gasket is
seated and the chamber is sealed.
Re-install evaporating chamber:
Reconnect the fill line.
Reconnect electrical plugs (the plugs are color coded).
Reconnect the drain union.
Reconnect the vapor hose.
Verify electrical connections:
Verify that all DIN rail-mounted components are securely
fastened to DIN rail.
Verify that all power terminal screws and lugs are tight
from power block to heaters. See torque specifications in
Table 36-1.
Verify that all plugs under the humidifier cover are
completely plugged in.
Move the drain valve lever back to the auto position.
Turn on the water supply.
Turn on the electrical power.
3. Off-season maintenance
Perform complete inspection and cleaning of the following:
– Heaters
– Probe rods
Skimmer port and water seal
– Humidifier tank
After cleaning, the humidifier should remain empty until