Specifications
Page 36 • DRI-STEEM CRUV Electric Humidifier Installation, Operation, and Maintenance Manual
Maintenance
Tap/softened water
Table 36-1:
CRUV torque specifications
Screw or lug location
Torque
in-lbs N-m
Power block 16 1.8
Contactor 16 1.8
Heater 
nut
8-32 (8.5 mm) nut 20 2.2
10-32 (9.5 mm) nut 25 2.8
Heater 
wire lug
6 gauge (10 mm
2
) wire 35 4.0
8 gauge (6 mm
2
) wire 25 2.8
10-14 gauge (<6 mm
2
) wire 20 2.2
mc_070710_1655-CRUV
Humidifier De-scaling Solution
Scale buildup on humidifier heaters acts as an 
insulator, reducing humidifier performance while 
increasing energy costs. To keep humidifiers 
operating as efficiently as possible, remove scale 
with DRI-STEEM's Humidifier De-scaling Solution, 
available for purchase from your DRI-STEEM 
representative or distributor.
The De-scaling Solution cleans without risk 
of corroding humidifier tanks or welds. The 
De-scaling Solution also cleans surfaces 
unreachable by hand scraping.
DRI-STEEM's Humidifier De-scaling Solution is 
the only approved cleaner/de-scaler for use with 
DRI-STEEM humidifiers. Use of other cleaners/
de-scalers may void your DRI-STEEM warranty.
PFBB
•  Install the probe and probe plug assembly. Verify ground 
wire is solidly connected to tank.
•  Secure the chamber cover, making sure the cover gasket is 
seated and the chamber is sealed.
•  Re-install evaporating chamber:
–  Reconnect the fill line.
–  Reconnect electrical plugs (the plugs are color coded).
–  Reconnect the drain union.
–  Reconnect the vapor hose.
•  Verify electrical connections:
–  Verify that all DIN rail-mounted components are securely 
fastened to DIN rail.
–  Verify that all power terminal screws and lugs are tight 
from power block to heaters. See torque specifications in 
Table 36-1.
–  Verify that all plugs under the humidifier cover are 
completely plugged in.
•  Move the drain valve lever back to the auto position.
•  Turn on the water supply. 
•  Turn on the electrical power.
3.  Off-season maintenance
•  Perform complete inspection and cleaning of the following:
– Heaters
– Probe rods
–  Skimmer port and water seal
– Humidifier tank
•  After cleaning, the humidifier should remain empty until 