Specifications

DRI-STEEM CRUV Electric Humidifier Installation, Operation, and Maintenance Manual • Page 3
Product overview
Figure 3-1:
Ultra-sorb dispersion
OM-7475
Figure 3-2:
Rapid-sorb dispersion
Figure 3-3:
Single or multiple tube dispersion
OM-2007
OM-2006
Overview
Figure 3-5:
Water level control for DI/RO water
option humidifier
Supply water connection
Float rod
Float ball
OM-7396
Humidifiers using tap or softened water
control water levels electronically using a
three-rod probe. The controller responds
with the above actions when the water level
reaches each rod.
Figure 3-4:
Water level control for tap/softened
water humidifier
VLC-OM-030
Fill valve opens when water
level is below this probe.
Low-water cutoff. Power to
heaters is cut if water level
drops below this probe.
Fill valve closes when water
level rises to this probe.
mc_030910_1335
Humidifiers using DI/RO water control water
levels using a float valve and low-water
cutoff switch.
mc_052710_1644
Dispersion options
Dispersion options shown on this page are available for CRUV
humidifiers. See the installation instructions beginning on Page 6.