Figure 8-1:
Vapormist (standard water models) field piping overview
7BQPSNJTUQJQJOHTUBOEBSEXBUFS
NPEFMT
Water supply line; water pressure must be
between 25 psi and 80 psi (175 kPa and
550 kPa); water conductivity minimum
100 μS/cm. If water piping to humidifier is
nonmetallic, we recommend that the first
3' (1 m) of water supply piping from the
humidifier be metallic
Steam vapor hose; may also use
pipe or tubing. See Table 16-1
for maximum piping lengths
Two keyholes for wall
mounting, 16" (406 mm)
on center
Unions by installer
Water supply line
Shock arrester
recommended to
reduce water hammer
¾" pipe thread
(DN20) tank drain,
skimmer and P-trap
piping, rated for
212 °F (100 °C). If
piping run is over
10' (3 m) increase
pipe to 1¼" (DN32)
after P-trap.
1" (25 mm) air gap
Spill funnel. Plumb
to floor drain.
Open drain required. See
first note below.
¾" pipe thread (DN20)
frame drain and
P-trap piping, rated
for 212 °F (100 °C)
Frame drain
Cover
Electrical conduit
knockouts provided
top and bottom:
t $PNCJOBUJPOGPS
½" and ¾" conduit
connectors (knock-
out diameters
22.3 mm and
28.6 mm)
t $PNCJOBUJPOGPS
¾" and 1" conduit
connectors (knock-
out diameters
28.6 mm and
34.9 mm)
Install plumb
DC-1136
Notes:
t -PDBUFBJSHBQPOMZJOTQBDFTXJUIBEFRVBUFUFNQFSBUVSFBOEBJSNPWFNFOUUPBCTPSCnBTITUFBNPUIFSXJTFDPOEFOTBUJPONBZGPSNPOOFBSCZTVSGBDFT3FGFS
to governing codes for drain pipe size and maximum discharge water temperature.
t 0GGTFUIVNJEJmFSGSPNTQJMMGVOOFMPSnPPSESBJOUPQSFWFOUnBTITUFBNGSPNSJTJOHJOUPUIFDBCJOFU
t %BTIFEMJOFTJOEJDBUFQSPWJEFECZJOTUBMMFS
t 5IFXBUFSTVQQMZJOMFUJTNPSFUIBONNBCPWFUIFTLJNPWFSnPXQPSUFMJNJOBUJOHUIFQPTTJCJMJUZPGCBDLnPXPSTJQIPOJOHGSPNUIFUBOL/PBEEJUJPOBM
backflow prevention is required; however, governing codes prevail.
t *OTUBMMBVOJPOJOUIFXBUFSTVQQMZBOEESBJOMJOFTBTTIPXOUPBMMPXUBOLSFNPWBM
t %BNBHFDBVTFECZDIMPSJEFDPSSPTJPOJTOPUDPWFSFECZZPVS%3*45&&.XBSSBOUZ
t 4FFUIFOFYUQBHFGPSSFDPNNFOEFEQJQJOHGPS7BQPSNJTU%*NPEFMTNPEFMTUIBUVTF%*30XBUFS
t 4FFUIFEJTQFSTJPOTFDUJPOPGUIJTNBOVBMGPSNPSFJOGPSNBUJPOBCPVUQJQJOHUIBUDPOOFDUTUIFIVNJEJmFSUPUIFEJTQFSTJPOBTTFNCMZ
2" (50 mm)
12" (300 mm)
2" (50 mm) water seal or loop
in the supply line to isolate
steam from nonmetallic supply
piping