DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 31
Figure 31-1:
Single dispersion tube with condensate drain
OM-7366X
Dispersion:
Single dispersion tube
Single dispersion tube with condensate drain
Mounting nut
3/8" - 16 (M10)
XT humidifier
Duct
Secure and seal
escutcheon plates
90° long sweep
or two 45° elbows
Pitch tube toward
drain 1/8"/ft (1%)
½" O.D. (DN15) condensate drain tube.
Pitch ¼”/ft (2%) toward escutcheon plate.
¾" (DN20) (minimum) condensate drain tube by installer.
Must be suitable for 212 °F (100 °C) water.
¼" NPT (DN8)
6" (150 mm)
recommended
Water seal
5" (125 mm)
1" (25 mm) air gap
Steam hose, tubing, or pipe (tubing or pipe must be
grounded). Insulate tubing and hard pipe to reduce
steam loss. Do not insulate steam hose. See Table
24-1 for maximum piping lengths.
Pitch*
Open drain required. Locate air gap only in spaces with adequate temperature and
air movement to absorb flash steam; otherwise, condensation may form on nearby
surfaces. Refer to governing codes for drain pipe size and maximum discharge water
temperature.
* Pitch steam hose, tubing, or pipe toward dispersion tube:
– 2"/ft (15%) when using steam hose
– ½"/ft (5%) when using 1½" tubing or pipe
Dashed lines indicate provided by installer.
See the first bullet in
Installation notes.
OM-351-1
3.25"
(82.5 mm)
3.25"
(82.5 mm)
Condensate drain
A
Dispersion tube
Dimension A:
3.25" (82.5 mm) for 1½" tubes
A
Escutcheon plates
mc_062810_0725-XT
Adapter
Installation