Specifications
Page 48 • DRI-STEEM XT Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Start-up procedure
Operation
Safety functions
XT humidifiers are protected against 
running dry — current does not flow if the 
electrodes in the steam cylinder are not 
submerged in water. 
If the current rating exceeds 120% of nominal 
current, the drain valve opens automatically. As 
the water level drops, the current rating drops 
back to the nominal value.
If the current rating exceeds 120% of the 
nominal current after several drainage 
operations, the humidifier shuts down 
automatically.
Capacity limitation
XT humidifier capacity can be limited to a 
user-specified maximum:
Using the keypad/display or Web interface, from 
the Main menu, and select Tank Setup, then 
select Capacity Adjustment for menu options.
After the system is installed and connected properly: 
1.  Verify that the humidifier, controls, piping, electrical 
connections, steam supply, and dispersion units(s) are installed 
according to the following:
•  Installation instructions in this manual
•  Vapor-logic4 Installation and Operation Manual 
– Installation section
– Installation checklist
•  Ladder style wiring diagram (inside humidifier cabinet)
•  External connections wiring diagram (inside humidifier 
cabinet)
•  All governing codes
2.  Verify that all electrical connections are secure before applying 
power. 
3.  Make sure all electrical covers are in place and secure. See 
Warning at left.
4.  Verify that the humidifier is mounted level and securely 
supported before filling with water. See operating weights in 
Table 4-1.
5.  Verify that the humidifier is level front to back and side to side 
after it is full of water.
6.  Read the “Operation” section of the Vapor-logic4 Installation 
and Operation Manual.
Note: During start-up, do not leave the humidifier unattended.
7.  Perform all applicable “Start-up checklist” items. See Page 49.
8.  Monitor humidifier operation through multiple fill cycles. The 
humidifier operating status appears on the keypad/display.
9.  Perform the cleaning procedure as follows:
a.  Operate the humidifier long enough for steam to be 
produced.
b.  Drain the cylinder completely using the keypad/display: 
– At the Main menu, select Tank Status, and press Enter. 
– Select Mode Auto, and press Enter. 
– Select Drain, and press Enter. 
– Let the cylinder drain for 5 to 10 minutes until empty. 
c.  Restart the humidifier, and repeat Steps a and b.
WARNING
Electric shock hazard
Only qualified electrical personnel should 
perform start-up procedure.
Contact with energized circuits can cause 
property damage, severe personal injury 
or death as a result of electrical shock or 
fire.
Make sure that all electrical covers are 
in place and secure before turning on 
electrical power. These include the heater 
terminal cover, electrical panel cover, and 
subpanel access panels.
XT humidifier and XTSB doors have lift-off hinges 
for easy removal of open doors. The doors are 
captivated when closed but should be removed 
when open. An upward bump could damage the 
door if it jumps the hinges and falls.