Fusing and line currents
Table 5-1:
Recommended fusing and line currents for XT humidifiers
Model Phase Volts
Line amps
kW
Recommended
fusing amps
L1 L2 L3
XT-5 1
120 14.2 14.2 1.7 25
208 8.2 8.2 1.7 15
230 7.4 7.4 1.7 13
240 7.1 7.1 1.7 15
XT-10
1
208 16.3 16.3 3.4 25
230 14.8 14.8 3.4 25
240 14.2 14.2 3.4 25
277 12.3 12.3 3.4 20
480 7.1 7.1 3.4 15
600 5.7 5.7 3.4 10
3
208 9.4 9.4 9.4 3.4 15
240 8.2 8.2 8.2 3.4 15
400 4.9 4.9 4.9 3.4 13
480 4.1 4.1 4.1 3.4 10
600 3.3 3.3 3.3 3.4 10
XT-20
1
208 32.2 32.2 6.7 50
230 29.1 29.1 6.7 50
240 27.9 27.9 6.7 45
277 24.2 24.2 6.7 40
480 14.0 14.0 6.7 25
600 11.2 11.2 6.7 20
3
208 18.6 18.6 18.6 6.7 30
240 16.1 16.1 16.1 6.7 25
400 9.7 9.7 9.7 6.7 16
480 8.1 8.1 8.1 6.7 15
600 6.4 6.4 6.4 6.7 10
XT-30 3
208 28.0 28.0 28.0 10.1 45
240 24.3 24.3 24.3 10.1 40
400 14.6 14.6 14.6 10.1 25
480 12.1 12.1 12.1 10.1 20
600 9.7 9.7 9.7 10.1 15
XT-50 3
208 46.6 46.6 46.6 16.8 70
240 40.4 40.4 40.4 16.8 70
400 24.2 24.2 24.2 16.8 40
480 20.2 20.2 20.2 16.8 35
600 16.2 16.2 16.2 16.8 25
XT-75 3
400 36.2 36.2 36.2 25.1 63
480 30.2 30.2 30.2 25.1 50
600 24.2 24.2 24.2 25.1 40
XT-100 3
400 48.4 48.4 48.4 33.5 80
480 40.3 40.3 40.3 33.5 70
600 32.2 32.2 32.2 33.5 50
XT-150 3
400 72.6 72.6 72.6 50.3 125
480 60.5 60.5 60.5 50.3 100
600 48.4 48.4 48.4 50.3 80
XT-200 3
400 96.7 96.7 96.7 67.0 150
480 80.6 80.6 80.6 67.0 125
600 64.5 64.5 64.5 67.0 100