Installation manual

12
4.3 Confirming Modules
Ref # [0202] then scroll to desired module
In case module numbers were not recorded, you can ver-
ify this information through the “Confirm Module”
menu in the “Module Hardware” programming section
in installer’s programming.
This works just like enrolling modules. You will be
prompted to “Press Any Key On Desired Unit” in the case
of keypads and “Create Tamper on Desired Unit” in the case
of modules. Once the correct action is taken, the keypad will
display the module number (e.g. LCD4501 Mod 02).
4.4 Enrolling AML Devices
Addressable Multiplex Loop (AML) devices use a 2-wire
connection for power and communication to and from
the control panel. All detectors are designed for low
power consumption to make for an efficient system.
For information on AML wiring, please see Section 2.8
“AML Device Wiring.”
Enroll the AML devices after all PC4108A, PC4164-RS
and PC4116 modules have been enrolled.
NOTE: Fire and burglary initiating devices can-
not be mixed on the same addressable loop.
Programming the PGM Terminal for an AML Loop
Ref #: [001400]
To enroll addressable multiplex loop (AML) devices, you
must first program the PGM terminal. Perform the fol-
lowing:
1. Enter Installer’s Programming and enter reference
number [001400].
2. To select PGM1 for AML devices, scroll to “PGM1
AML?” and press [*]. The option will toggle to Yes.
NOTE: Do not turn off the PGM AML toggle option
unless all AML devices have been removed from the
loop (see “Removing AML Devices”).
To Enroll an AML Device
Ref #: [00140300] for PGM1
NOTE: All AML devices must be connected before
they are enrolled.
To enroll the device, perform the following:
1. Enter Installer’s Programming and enter reference
number [00140300].
2. Enter the 5-digit serial number on the detector to be
enrolled.
3. If the correct serial number was entered, the panel will
allow you to select the zone that the addressable detector
will be assigned to. Any zone from zone 009 to 064 on
the PC4010 can be used as an AML zone. If the detector
is not connected to the PGM terminal, the zone will not
be enrolled. Do not use zones designated for Access Control.
Repeat from Step 2 until all AML devices have been enrolled.
If the zone serial number is already programmed into the
panel, the panel will display the message “Already
Enrolled” on the top line of the LCD and the serial num-
ber on the bottom line of the LCD for three seconds. The
panel will then display the zone assignment for the
device. This allows for the reassignment of an existing
zone or to verify programming.
NOTE: Only the AMS-220/220T devices may be
defined as fire zones. Do not program other AML
devices as fire zones.
Panel Key
Ref #: [001401]
IMPORTANT NOTE: To ensure system security, the panel
key must be programmed when using AML devices.
The Panel Key is a 2-digit code that acts as a security lock
for the AML detectors. Once you have enrolled all AML
zones, you must change the panel key from [00] to
another 2-digit number (01-FF). When the panel key is
changed, the panel broadcasts the new code to each
addressable device. Any device added to the system
with a panel key other than the one programmed or the
default [00] will not function.
When an addressable device is deleted, panel repro-
grams the device’s Panel Key to 00. This allows the
device to be re-enrolled on another system.
Moving AML Devices
To another zone on the same loop
1. Enter Installer’s Programming and enter reference
number [00140300].
2. Enter the device’s 5-digit serial number. The keypad
display will read “Already Enrolled [serial number]”
to indicate that the device has already been enrolled.
3. After three seconds, the display will indicate the
device’s zone assignment. Enter the new zone num-
ber. Any zone from zone 009 to 064 on the PC4010
can be used as a AML zone.
4. The zone definition and attributes must also be pro-
grammed for the new zone.
Removing AML Devices
Ref #: [00140301] for PGM1
When removing AML devices, they must be deleted
from the loop. If the device is not deleted, its panel key
will not be reset to [00].
To remove an AML device from the system, perform the
following:
1. For devices to be deleted: Enter Installer’s Program-
ming and enter ref# [00140301].
2. The display will read “Serial# [ ]” on the top line of
the display and the zone label on the bottom line of
the display. Use the [<][>] keys to scroll to the zone to
be deleted then press [*]. The bottom line of the dis-
play will then read “Zone Deleted.”
3. To delete all AML devices from the selected PGM
output, select Default AML. The panel will display
“Confirm Default Press [*]”. To delete all AML
devices on the selected PGM, press [*].