Specifications

G E T T I N G S T A R T E D
7
Ensure the plugs and jacks meet the dimension, tolerance and metallic plating requirements of 47
C.F.R. Part 68, SubPart F
.
For proper operation there must be no other telephone equipment connected between the control
panel and the telephone company facilities
.
Do not connect the alarm panel communicator to telephone lines intended for use with a FAX ma-
chine. These lines may incorporate a voice filter which disconnects the line if anything other than FAX
signals are detected, resulting in incomplete transmissions
.
2.3 Keybus Operation and Wiring
The Keybus is used by the panel to communicate with all modules connected and by the modules to talk to
the panel. The RED and BLK terminals are used to provide power while YEL and GRN are clock and data.
The 4 Keybus terminals of the panel must be connected to the 4 Keybus terminals or wires of all modules.
The following conditions apply:
Keybus should be run in minimum 22 gauge quad (0.5mm), two pair twist preferred
the modules can be home run to the panel, connected in series or can be T-tapped
any module can be connected anywhere along the Keybus, you do not need a separate Keybus wire
run for keypads, zone expanders etc.
no module can be more than 1,000'/305m (in wire length) from the panel
shielded wire is not necessary unless wires are run in an area that may present excessive RF noise or
interference
Example of Keybus Wiring
B
C
A
PANEL
500’
500’
150’
150’
B
C
A
PANEL
500’
500’
150’
150’
NOTE: Module (A) is wired correctly as it is within 1,000'/305m of the
panel, in wire distance.
Module (B) is wired correctly as it is within 1,000'/305m of the
panel, in wire distance
Module (C) is NOT wired correctly as it is further than 1,000'/
305m from the panel, in wire distance.
2.4 Current Ratings - Modules and Accessories
In order for the Power 832 system to operate properly, the power output capabilities of the main control
and expansion devices must not be exceeded. Use the data presented below to ensure that no part of
the system is overloaded and cannot function properly.
System Outputs (all 12 V
DC)
PC5010 VAUX: 500 mA. Includes one keypad. Subtract for each additional keypad, expansion module
and accessory connected to VAUX or Keybus.
BELL: 700 mA. Continuous Rating.
3.0 A. Short Term. Available only with stand-by battery connected.
PC5204 VAUX: 1.0 A. Continuous Rating. Subtract for each device connected.
3.0 A. Short Term. Available only with stand-by battery connected.
PC5208 VAUX: 250 mA. Subtract for each device connected. Subtract the total load on this terminal
from the PC5010 VAUX/Keybus output.
PC5100 VAUX: 100 mA. Subtract for each device connected. Subtract the total load on this terminal
from the PC5010 VAUX/Keybus output.
PC5108 VAUX: 100 mA. Subtract for each device connected. Subtract the total load on this terminal
from the PC5010 VAUX/Keybus output.
PC5010 Device Ratings (@ 12 V
DC)
LCD5500 Keypad: 50 mA PC5208 Output Module: 50 mA
PC5532 Keypad: 45 mA PC5132 Wireless Module: 125 mA
PC5516 Keypad: 45 mA PC5100 Addressable Service Interface Module: 40 mA
PC5508 Keypad: 45 mA Escort5580 Module: 150 mA
LCD5500Z Keypad: 85 mA PC5928 Audio Interface Module: 65 mA
PC5532Z Keypad: 85 mA PC5921 Intercom Audio Station: 20 mA
PC5516Z Keypad: 85 mA PC5921 EXT Door Box Audio Station: 20 mA
PC5508Z Keypad: 85 mA PC5921 EXT/R Door Box Audio Station: 35 mA
PC5108 Zone Module: 35 mA PC5400 Printer Module: 65 mA
PC5204 Output Module: 20 mA