PowerSeries PC1616/PC1832/PC1864 version 4.2 NA Installation Guide WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability the manufacturer. The entire manual should be carefully read.
Table of Contents Section Description Page 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 Installation & Wiring............................................................................................ 1 Keybus Wiring .................................................................................................. 2 Zone Wiring...................................................................................................... 2 Zone Expanders............................................................
Section 1: Installation & Wiring Section 1: Installation & Wiring This Installation Guide provides the basic installation, wiring and programming information required to program the PowerSeries PC1616, PC1832 and PC1864 control panels. This guide shall be used in conjunction with the PowerSeries PC1616/1832/1864 Reference Manual which can be obtained from your local dealer or downloaded from the DSC web site at www.dsc.com.
PowerSeries - PC1616/PC1832/PC1864 1.1 Keybus Wiring The 4-wire KEYBUS (red, black, yellow and green) is the communication connection between the control panel and all modules. The 4 KEYBUS terminals of all modules must be connected to the 4 KEYBUS terminals of the main control panel.
Installation PC1616/1832/1864 Wiring Diagram North America Only POWER LIMITED Stand Off PC Board Cable Tie (not supplied) recommended Cabinet 2. Position circuit board mounting holes over standoffs. Press firmly on board to snap-in-place. DSC UA503 Primary:120VAC/60Hz. Secondary: 16.5VAC 40VA DSCPTD 1640U Class II Transformer 220 1. Inser t Stand off into cabinet mounting hole in the desired location. Snap-inplace.
PowerSeries - PC1616/PC1832/PC1864 1.5 AUX Power Wiring The control panel can provide a maximum of 700mA of current for modules, powered detectors, relays, LED’s etc. If the total current required exceeds 700mA an additional power supply is required (e.g.,PC5200, PC5204). See list below. Min/max operating voltages for devices, sensors and modules is 9.5VDC - 14VDC Refer to the list of Compatible Devices on page 1 and/or the Reference Manual for the current draw of individual devices 1.
Section 2: User Commands Section 2: User Commands Any system keypad can be used to program or perform any keypad command. LED keypads use status and zone indicator lights to represent alarm functions and status. The LCD keypad displays the description and status indicator lights represent alarm functions and status. This section describes basic keypad commands. Refer to the PC1616/1832/1864 Reference Manual for detailed description of all keypad commands.
PowerSeries - PC1616/PC1832/PC1864 [ ][2] Trouble Display Refer to Appendix D – Trouble Conditions, for troubleshooting assistance and a detailed description of all trouble conditions. Press [8] on any keypad or [ ] on the trouble on any PK series keypad to enter the time and date programming menu. This option will be available if a Loss of Clock trouble is present on the system. A General System Supervisory caused by a hardwired or wireless zone expander cannot be overidden by this method.
Section 2: User Commands [ ][6] – User Functions Press [ ][6] followed by the Master Code, then press the number corresponding to the following functions. [1] Program Time and Date: Enter the time and date using the following format [HH:MM] [MM/DD/YY]. Program the time using military standard (e.g., 8:00 pm = 20:00 hours). [2] Auto-arm/Auto-disarm Enable/Disable: The keypad will emit 3 rapid beeps if the Auto-arm/Auto-disarm feature is now enabled and a steady 2-second tone if it is now disabled.
PowerSeries - PC1616/PC1832/PC1864 Section 3: Programming This section provides the information necessary to program all required features for a basic system as well as common applications. Refer to the PC1616/1832/1864 Reference Manual for a complete description of all programmable features. 3.1 Template Programming Selecting [ ][8] [Installer Code] [899] displays the current 5 digit template programming code.
Section 3: Programming The Armed and Ready lights indicate programming status: Armed Light ON Ready Light ON Ready Light FLASHING Panel waiting for 3-digit section number If in module programming, waiting for section # to be entered. Panel waiting for data to be entered Panel waiting for HEX data to be entered You cannot enter installer programming while the system or any partition is armed or in alarm. 3.3.1 Programming Toggle Options: Enter the 3-digit programming section number.
PowerSeries - PC1616/PC1832/PC1864 Section 4 – Programming Descriptions The following is a brief description of the features and options available in the Power PC1616/1832/1864 control panel. Refer to the PC1616/ 1832/1864 Reference Manual for a complete description of all programming features, limitations and requirements.
Section 4 – Programming Descriptions [36] 24-hr. Non-Latching Tamper Zone: Instant tamper condition when violated. Active in both the armed and disarmed state.
PowerSeries - PC1616/PC1832/PC1864 [18] Stay Armed Status: Activates when all of the selected partitions are armed in Stay mode [19] Command Output 1:Activates when a [ ][7][1] command is entered on the selected partition – Command can be programmed to require a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
Section 4 – Programming Descriptions [5] ON: auto-arming schedules (Program Sections [181]-[188]) will be available to the user in the [ ][6] menu. OFF: auto-arming schedules will NOT be available to the user in the [ ][6] menu. [6] ON: the Audible Exit Fault feature will be enabled. If a delay zone is not secured correctly and not force-armed, at the end of the exit delay, the system will go into entry delay and turn ON the bell output.
PowerSeries - PC1616/PC1832/PC1864 [8] ON: the system activates the bell output if a telephone line trouble is detected while the system is armed. OFF: the system activates the keypad buzzer trouble tone. Section [016] Fourth System Option Code Option Description [1] ON: the system supervises the AC input and displays a trouble if a failure is detected. OFF: AC Input is not supervised. [2] ON: the trouble light will flash when an AC trouble is detected.
Section 4 – Programming Descriptions [5] ON: the keypad buzzer follows the bell output for all alarms. OFF: the system only activates the bell output for all alarms. [6] ON: When an alarm is detected on a zone (with the Cross Zone attribute enabled), a timer is started. The alarm is not transmitted and the bell output is not activated unless a second cross zone enabled zone is violated before the Cross Zone timer times out.
PowerSeries - PC1616/PC1832/PC1864 [5] For Future Use [6] Refer to the PC1616/PC1832/PC1864 Reference Manual for RF Delinquency details. [7] Future Use [8] ON: When the system is armed in Stay mode, during the Exit delay, the system will sound 1 beep every 3 second. OFF: When the system is armed in Stay mode, the system will be silent during the Exit delay.
Section 4 – Programming Descriptions [9] ON: the zone has the Cross Zone feature enabled. OFF: the zone functions normally.
PowerSeries - PC1616/PC1832/PC1864 Section [170] PGM Output Timer Program the time, in seconds, PGM outputs programmed to follow the PGM Output Timer will activate for. Valid entries are [001] to [255]. Section [171] Tamper PGM Output Timer Program the time, in minutes, that a tamper condition will latch the Tamper PGM output. Valid entries are [000] to [255]. Section [175] Auto-arm Postpone Timer Program the time, in minutes, that the system will postpone automatic arming.
Section 4 – Programming Descriptions different format, this account number will be used for all events that are not partition specific (for example, low battery, AC trouble etc.). For partition specific events the system will use the programmed Partition Account Number. For all formats other than SIA, program a HEX [A] for any digit [0] in the account number being used.
PowerSeries - PC1616/PC1832/PC1864 Section [379] Periodic DLS Time of Day Programs the time the system will auto-call DLS. Program 4 digits – [HH][MM] using military standard. For a DLS auto-call at 11:00 pm, program data [23][00]). Valid entries are [00][00] to [23][59]. Programming [99][99] will select a random time, [FF][FF] will disable it. Please refer to the PC 1616/1832/1864 Reference Manual for a complete description of Periodic DLS.
Section 4 – Programming Descriptions [3] ON: the keypad will display the message ‘Communications Cancelled’ (programmable LCD) or ‘CC’ (fixed-message LCD) upon successful transmission of the Communication Cancelled reporting event. OFF: the keypad will not display these messages. [4] ON: the system dials the Call Waiting Cancel String on the first attempt to dial the central station. OFF: the system does not dial the Call Waiting Cancel String. [5] ON: enables support for the T-Link module.
PowerSeries - PC1616/PC1832/PC1864 Section [404] Panel Identification Code Program the 6-digit Panel Identification Code. This code is used by the downloading computer to verify the correct account is calling back (Call Back feature) or to identify which customer account file should be used (User Initiated DLS and Auto Event Buffer Upload features). Section [405] Double-Call Timer Program the maximum time, in seconds, between calls when connecting to panel using the double call feature.
Section 4 – Programming Descriptions [3] ON: PGM output activates if a Panic Alarm occurs. [4] ON: PGM output activates if a Medical Alarm occurs. [5] ON: PGM output activates if a Supervisory Alarm occurs. [6] ON: PGM output activates if a Priority Alarm occurs. [7] ON: PGM output will activates if a 24-Hour Hold-Up Alarm occurs. [8] ON: the PGM output activates for the time programmed for the PGM Output Timer. OFF: the PGM output will latch until a valid user code is entered.
PowerSeries - PC1616/PC1832/PC1864 Section [601] to [608] Additional Reporting Codes Program the reporting code for all events to be transmitted. For description of when each reporting event will be transmitted, refer to Appendix A – Reporting Codes. The panel also supports Automatic SIA and Automatic Contact ID reporting. Program data [00] to disable the reporting of an event.
Section 4 – Programming Descriptions Section [703] Delay Between Dialing Attempts Program the time the panel will wait between dialing attempts to transmit a reporting event to the central station. Valid entries are [001] to [255]. Section [800]-[851] Module Programming The following program sections are used to program different modules that can be connected to the control panel.
PowerSeries - PC1616/PC1832/PC1864 Section [904]: Wireless Placement Test Enter Section [904] followed by the 2-digit number of the wireless zone to test. When a wireless signal is received from the selected transmitter, the system will indicate the location as Good or Bad as follows: Good: Bad: One bell squawk, 1 keypad beep, keypad zone light [1] ON Three bell squawks, 3 keypad beeps, keypad zone light [3] ON Press [#] to exit when testing is complete.
Section 5: Programming Work Sheets Section 5: Programming Work Sheets 5.1 Index to Programming Work Sheets Programming Option Page [000] Keypad Enrollment .....................................................................28 [001]-[004] Zone Definitions................................................................28 [005] System Times.............................................................................29 [006] Installer’s Code...................................................................
PowerSeries - PC1616/PC1832/PC1864 5.2 Programming Worksheets Shaded programming sections indicate minimum programming requirements SIA FAR CP-01 defaults are indicated in gray text. Keypad Partition /Slot and Function Key Programming [000] Keypad Enrollment This must be done at each keypad requiring programming. [0] [1] [2] [3] [4] [5] Slot address [Valid entries are 0-8 for the partition, 1-8 for the slot. (e.g.
5.2 Programming Worksheets Section Zone Def. Section Zone Def. Section Zone Def.
PowerSeries - PC1616/PC1832/PC1864 [006] Installer’s Code [007] Master Code [008] Maintenance Code Default 5555 I_______I_______I_______I_______I Default 1234 Default AAAA I_______I_______I_______I_______I I_______I_______I_______I_______I Programmable Output Options 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 Residential Burglary and Fire Bell Output 18 For Future Use 19 Sensor Reset [*][7][2] 20 2 Wire Smoke Support (PGM 2 only) 21 System Armed Status 22 Ready To Arm 23 Keypad Buzzer Follow M
5.
PowerSeries - PC1616/PC1832/PC1864 [017] Fifth System Options Opt Def 1 9 R 2 R R R R R R R 3 4 5 6 7 8 ON OFF WLS Key Does NOT use Access Codes RF Jam Log after 5 Minutes Audible RF Jam Trouble Beeps Double Hit Enabled Late to Close Enabled Daylight Savings Time Enabled For Future Use Squawk on Away Key Arming/Disarming Only 9 9 9 9 9 9 9 R R R R R R R R WLS Key Uses Access Codes RF Jam Log after 30 Seconds Silent RF Jam Trouble Beeps Double Hit Disabled Late to Close Disabled Daylight Savings
5.
PowerSeries - PC1616/PC1832/PC1864 [101]-[164] Zone Attributes Zone Attribute Defaults (Y = Option ON; N = Option OFF): Bold entries are opposite for SIA CP-01 Attribute: ON OFF 1 2 3 4 5 6 7 8 9 Audible Silent Steady Pulsed Chime No Bypass No Force* No Swing No Tx.
5.2 Programming Worksheets Attribute: 10 ON OFF 17 24hr Emergency 18 24hr Sprinkler 19 24hr Water 20 24hr Freeze 21 24hr Latching Tamper 22 Momentary Keyswitch 23 Maintained Keyswitch 25 Interior Delay 26 24hr Non-alarm 29 Auto Verified Fire 30 Fire Supervisory 31 Day Zone 32 Instant Stay/Away 35 24 hr Bell/Buzzer 36 24hr Non Latching Tamper 37 Night Zone 87 Dly. 24hr Fire (Wireless) 88 Stand.
PowerSeries - PC1616/PC1832/PC1864 Section Zone # Zone Type** Audible/ Silent 1 Steady/ Pulsed 2 Chime No 3 Bypass No 4 Force* No 5 Swing No 6 Tx.
5.
PowerSeries - PC1616/PC1832/PC1864 No Activity Arming Timers - Default is [000] for all partitions Section Partition [191] [192] [193] [194] [195] [196] [197] [198] 1 I_______I_______I_______I Valid entries are 001-255 minutes, 000 to disable 2 I_______I_______I_______I Valid entries are 001-255 minutes, 000 to disable 3 I_______I_______I_______I Valid entries are 001-255 minutes, 000 to disable 4 I_______I_______I_______I Valid entries are 001-255 minutes, 000 to disable 5 I_______I_______I_
5.2 Programming Worksheets Communications [301] First Telephone Number (32 Digits) I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I When using T-Link, program DCAA as the phone number.
PowerSeries - PC1616/PC1832/PC1864 [324]-[327] Alarm Restoral Reporting Codes, Zones 01-64 Section [324] [325] [326] [327] Zone 01 Zone 02 Zone 03 Zone 04 Zone 05 Zone 06 Zone 07 Zone 08 I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I Zone 09 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I____
5.
PowerSeries - PC1616/PC1832/PC1864 [344] Miscellaneous Opening (Disarming) Reporting Codes I_______I_______I For Future Use I_______I_______I For Future Use I_______I_______I For Future Use I_______I_______I For Future Use I_______I_______I For Future Use I_______I_______I Auto Arm Cancellation/Postpone I_______I_______I Special Opening [345] Maintenance Alarm Reporting Codes [346] Maintenance Restoral Reporting Codes I_______I_______I Battery Trouble Alarm I_______I_______I Battery Trou
5.2 Programming Worksheets [350] Communicator Format Options Default 04 I_______I_______I1st Telephone Number 04I_______I_______I2nd Telephone Number 01 20 BPS, 1400 HZ handshake 05 Pager 08 10 BPS, 2300Hz handshake 11 For Future Use 02 20 BPS, 2300 HZ handshake 06 Residential Dial** 09 Private Line 03 DTMF CONTACT ID 07 10 BPS, 1400Hz handshake 10 Scantronics 04 SIA FSK **Failure to communicate using Residential Dial will not generate a Failed To Communicate Trouble.
PowerSeries - PC1616/PC1832/PC1864 [375] System Maintenance Communicator Call Directions Option 2 Option 1 2nd Telephone 1st Telephone Number (Def ON) Number (Def OFF) Section I________I [375] Option 3 Not Used (Def OFF) Option 4 Not Used (Def OFF) Option 5 Alt Comm (Def ON) Options 6,7,8 Future Use I________I I________I I________I I________I Option 3 Not Used (Def OFF) Option 4 Not Used (Def OFF) Option 5 Alt Comm (Def ON) Options 6,7,8 Future Use I________I I________I I________I I______
5.
PowerSeries - PC1616/PC1832/PC1864 [402] DLS Downloading Telephone Number (32 Digits) |____D___|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______|_______| [403]-[404] DLS Downloading Access Code / Panel ID Code (Enter 6 Hexadecimal Digits) Panel Default [403] Downloading Access Code [404] Panel ID Code PC1616 16160
5.2 Programming Worksheets 1 Attribute: PGM Option 2 3 4 5 6 7 8 ON Serv. req. AC Fail TLM Fault FTC Zone Fault Zone Tmp. Zn. Low Bat. Loss of Clock OFF Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Y Y Y Y Y Y Y Y ON Burg. Evnt. Fire Evnt. Panic Evnt. Med. Evnt. Supv. Evnt. Priority Evnt. Holdup Evnt.
PowerSeries - PC1616/PC1832/PC1864 PGM Output Partition Assignment Section PGM # Main Board [551] 1 [552] Partition: 1 2 2 3 4 5 6 7 8 I________I I________| I________| I________| I________| I________| I________| I________I I________I I________| I________| I________| I________| I________| I________| I________I Main Board / PC5208 [553] 3 I________I I________| I________| I________| I________| I________| I________| I________I [554] 4 I________I I________| I________| I___
5.
PowerSeries - PC1616/PC1832/PC1864 [695] Holiday 1 Holiday 2 Holiday 3 Holiday 4 Holiday 5 Holiday 6 Holiday 7 I____I_____II_____I_____II_____I_____I I____I_____II_____I_____II_____I_____I I____I_____II_____I_____II_____I_____I I____I_____II_____I_____II_____I_____I I____I_____II_____I_____II_____I_____I I____I_____II_____I_____II_____I_____I I____I_____II_____I_____II_____I_____I Holiday 8 Holiday 9 Holiday 10 Holiday 11 Holiday 12 Holiday 13 Holiday 14 I____I_____II_____I_____II_____I_____
Module Programming Module Programming [801] PC5400 Printer Module Programming Refer to the PC5400 Installation Manual for installation and programming instructions. [802] PC59xx VOX Module Programming Refer to the PC59xx Installation Manual for installation and programming instructions. [804] PC5132 Wireless Expansion Programming Refer to the PC5132 Installation Manual for programming locations and instructions.
PowerSeries - PC1616/PC1832/PC1864 For the Record Customer: ___________________________________________________________________________________________________________ Address: ____________________________________________________________________________________________________________ Telephone: ______________________________________________Installation Date:_____________________________________________ Installers Code: _______________________________________________________________________________________
Module Programming Zone Programming Summary Zone programming can be found in sections [001] - [004], [101] - [164], [020], [202]-[265]. Use this area to record a summary of your zone programming.
PowerSeries - PC1616/PC1832/PC1864 Appendix A: Reporting Codes The following tables contain Contact ID and Automatic SIA format reporting codes. For more information on reporting code formats and notes about individual reporting codes, (see Section 5.6 Communicator Programming PWS Sect 6). Contact ID The first digit (in parentheses) will automatically be sent by the control. The second two digits are programmed to indicate specific information about the signal.
Appendix A: Reporting Codes Dialer Direction* Automatic Contact ID Codes SIA Auto Rep Codes** Section # Reporting Code Code Sent When... [345]-[346] Auxiliary Power Trouble/ Rest. Aux voltage supply trouble/restoral MA/R (3) 12 YP-00/YQ-00 [345] TLM Failure Telephone line monitoring trouble MA/R (3) 51 LT-01 [346] TLM Restore Telephone line restored MA/R (3) 51 LR-01 [345]-[346] Gen System Trouble/Rest.
PowerSeries - PC1616/PC1832/PC1864 Appendix B: UL Listed Commercial and Residential Installations The installation requirements listed below must be met for the following grades of service. Central Station and Police Connect (Standard or Encrypted Line Security Service) The installation must use T-Link module which communicates over LAN/WAN to the Sur-Gard MLR-IP receiver or the TL200/250 which communicates over LAN/ WAN/Internet to the SG System III receiver. Polling time must be 90 seconds.
Appendix C: SIA False Alarm Reduction Appendix C: SIA False Alarm Reduction SIA Feature Programming Section Comments Range/Default Requirement Exit Time [005], 3rd entry Access to Entry and Exit delays for each partition and Bell Time Out for the system For Full or auto arming: Range:45- 255 seconds Default: 60 sec.
PowerSeries - PC1616/PC1832/PC1864 Appendix D: Troubleshooting Guide Testing: • • Power up system Program options as required (See Programming Section) NOTE: For advanced programming refer to the PC1616/1832/1864 Reference Manual • • Violate, then restore zones Verify correct Reporting Codes are sent to the Central Station Troubleshooting: LCD Programmable-Message Keypad • • • Press [✱][2] to view a trouble condition.
Appendix D: Troubleshooting Guide Trouble Cause Trouble [1] Service Required [1] Low Battery Troubleshooting Press [1] to determine specific trouble Main panel battery less than 11.1VDC NOTE: This trouble condition will not clear until the battery voltage is 12.5VDC min., under load. [2] Bell Circuit Bell+, Bell-...Open Circuit NOTE: If battery is new allow 1 Hr. for battery to charge. • Verify voltage measured across AC terminals is 16-18 VAC. Replace transformer if required.
PowerSeries - PC1616/PC1832/PC1864 Trouble Cause Troubleshooting No AC at panel AC input terminals Verify voltage measured across AC terminals is 16-18VAC. Replace transformer if required. Trouble [2] AC Failure Trouble [3] Telephone Line Trouble Phone Line Voltage at TIP, RING on main panel less than 3VDC • • Measure the voltage across TIP and RING on the panel: • No phone off-hook – 50VDC (approx) • Any phone off-hook – 5VDC (approx) Wire incoming line directly to TIP and RING.
Appendix D: Troubleshooting Guide Trouble Cause Troubleshooting Trouble [5] Zone Fault (Cont.) One or more wireless devices have not checked in within the programmed time • • A short circuit is present on one or more zones with double end-of-line resistors enabled • • Trouble [6] Zone Tamper Remove the wire leads from Z and COM terminals and measure the resistance of the wire leads. • A short circuit indicates a short in the wiring. Connect a 5.
PowerSeries - PC1616/PC1832/PC1864 Appendix E: Template Programming Template programming allows quick programming of the minimum functions required for basic operation. The below tables are used to determine the desired template to be used ( for information on performing template programming see Section 4 – Programming Descriptions). Each digit represents 1 of the template sections listed below. The option number selected for each digit will make up the 5 digit template programming code.
Appendix E: Template Programming • Digit 4 selects reporting code configurations Option Common Group Selected Troubles Openings/ Closings Zone Restorals DLS/Installer Lead In/Out 1 2 3 4 5 6 7 8 indicates included, Blank indicates default setting, indicates disabled Common Group Description Phone 1 Phone 2 Sections Set all Reporting Codes to automatic [320] - [349], [601] - [608] FF Alarm/Restore call directions enabled [351][1] ON, [2] OFF Tamper/Restore Call directions disabled [359][1
PowerSeries - PC1616/PC1832/PC1864 Openings & Closings Users CLOSINGS, Residential Dial Reporting codes Section 1-8 51 52 53 54 55 56 57 58 [339] 9-16 61 62 63 64 65 66 67 68 [339] 17-24 71 72 73 74 75 76 77 78 [340] 25-32 81 82 83 84 85 86 87 88 [340] 33-40 FF FF FF FF FF FF FF 98 [601] Users OPENINGS, Residential Dial Reporting codes 1-8 11 12 13 14 15 16 17 18 [342] 9-16 21 22 23 24 25 26 27 28 [342] 17-24 31 32 33 34 35 36
Note to Installers Limited Warranty This warning contains vital information. As the only individual in contact with system users, it is your responsibility to bring each item in this warning to the attention of the users of this system. Digital Security Controls warrants the original purchaser that for a period of twelve months from the date of purchase, the product shall be free of defects in materials and workmanship under normal use.
FCC COMPLIANCE STATEMENT CAUTION: Changes or modifications not expressly approved by Digital Security Controls could void your authority to use this equipment. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.