Specifications
DSX Access Systems, Inc. 10731 Rockwall Road Dallas, Texas 75238 / 888-419-8353 / 214-553-6140 / www.dsxinc.com
11/2012
Dial-Up Modem Communications from the DSX-1042 Master 
Controller to the PC utilizes a DSX modem at the Controller 
and one at the PC. At the DSX-1042 Master, the RS-232 Host 
Communications Port connects to the Modem. The Modem 
derives its power from the DSX-1042 panel. The Controller 
auto-dials to the PC all Alarm and Supervisory conditions. The 
Controller can also be programmed to dial the PC when its 
event storage buffer is 80% full. 
Controller Communications is handled at each DSX-1048 by a 
DSX-1040CDM (communications distribution module) using 
true point to point, regenerative, RS-485, 4-wire 
communications. This module has 2 RS-485 ports for in and 
out 4 wire communications to other Controllers. The 
Controller network communications is regenerated at each 
DSX-1040CDM allowing up to 4000 feet of distance between 
Controllers over two twisted pair cable. The DSX-1040CDM 
has 2 RS-232 Communication Ports. One is used to connect to 
the Master Controller and is only used in the DSX-1048PKG 
Enclosure where the Master Controller resides. The other RS-
232 port connects to the RS-232 port of each Slave Controller 
in that same enclosure. DSX-1048PKG Controllers are 
connected in a series loop configuration unless a DSX-1035 
Quadraplexor is used for Star wiring. 
DataBase Downloads 
The Controllers utilize a synchronized database that is 
maintained with the incremental and automatic or scheduled 
downloading of changes only. This intelligent, independent 
processing increases the speed of the panel’s actions and 
reactions, providing more stability and security to the overall 
system. The Controllers are downloaded with all parameters 
the first time they are brought on-line. Once the initial full 
download occurs all database changes such as the adding and 
deleting of card holders are sent to the Controllers by way of 
incremental downloads. The Controllers’ transaction buffer 
automatically adjusts its size to utilize any RAM not allocated 
for data. 
Diagnostic, Supervisory and Status LEDs 
The DSX-1048 has 88 diagnostic LEDs to indicate panel 
status. Thirty two are for Input Status, and sixteen are for 
Output Status. The rest are for Communications, Fuse Status, 
and Processor Status. 
DSX-1048 Specifications 
Size 
DSX-1040E Cabinet 15.5" W x 22.5" H x 6" D 
DSX-1040CDM 11" W x 4.5" H x 1.5" D 
DSX-1042 11" W x 4.5" H x 1.5" D 
Weight 
DSX-1040E Cabinet 19.2 lb. 
DSX-1040CDM 1.0 lb. 
DSX-1042   1.2 lb. 
DSX-1048 - Total 25.0 lb. 
Finish 
Black Powder Coat with White Silkscreen on Enclosure and 
Black Enamel on DSX-1042. 
Enclosure / Conduit Knockouts 
Concentric knockouts in Top, Bottom, and Sides. 
Knockouts accommodate 1/2, 3/4, 1, 1 3/4 inch conduit. 
Nema Type 1 equivalent enclosure with lift-off hinged door, 
lock/key, and tamper switch. 
Temperature 
Operating 32 to 131 F 
Storage -35 to 150 F 
Humidity 
Operating 0 to 95%, relative 
Power Requirements 
DSX-1042 13.5 VDC @ 300ma from 1040CDM 
DSX-1040CDM 13.5 VDC @ 150ma from 1040PDP 
Total Maximum Current 13.5 VDC @ 6.0A 
Output Voltage 
Panel outputs provide a regulated, fused, DC voltage. 
DSX-1042 9-13.5VDC - 12VDC nominal - 1A Fused 
DSX-1040CDM 9-13.5VDC - 12VDC nominal - 1.5A Fused 
DSX-1040CDM 5VDC - .5A Fused 
All Outputs are Class II, Power Limited 
Inputs 
EOL Supervised 32 
16 Inputs are used for standard point monitoring. 
16 Inputs are used for door position and exit request 
monitoring. 
All Inputs support two, three, and four state monitoring with 
five programmable circuit types. 
Outputs 
Form C Relays 8 
Relay Output Ratings 5 AMP - 30VDC 
Open Collector Outputs 8 - negative 100ma 
LED Outputs 24 - 3 per reader port - negative 100ma 
Pre-Alarm Outputs 8 - 1 per door - negative 100ma 
Access Controlled Entry Points 
Card Reader or Keypad 8 
Card and Reader Formats 240+ including FIPS/TWIC 
Any combination of card readers, keypads, or card and keypad 
controlled entry points may be used. 
Communication Ports 
DSX-1042 
RS-232 In 1 Master to PC 
RS-232 Out 1 Panel to DSX-1040CDM 
1040CDM 
RS-232 In 1 Master to DSX-1040CDM 
RS-232 Out 1 Slave Communications 
RS-485 In 1 From previous DSX-1048 Package 
RS-485 Out 1 To subsequent DSX-1048 Packages 
Processor 
AM186 20Mhz 
RAM/ROM Memory 
Flash ROM 512K 
Standard RAM 512K 
Warranty - Limited 2 Years 