WARNING
Loss of explosion protection
The Aloxy Pulse can only be used within a process temperature range of -40°C ≤ Ta ≤ +70°C when
mounted on pipes or machines.
CAUTION
Loss of type of protection
Damage to device if the enclosure is open or not properly closed. The type of protection specified
on the nameplate or in technical data is no longer guaranteed.
Make sure that the device is securely closed.
NOTICE
Incorrect mounting
The device can be damaged, destroyed, or its functionality impaired through improper mounting.
Before installing ensure there is no visible damage to the device.
Mount the device using suitable tools.
NOTICE
Torque
on
screws
regarding
plastic
mounting bracket
Device damage. The maximum torque of the mounting plate must not be exceeded 1 Nm (0.73 ft lb).
6 Usage of the Aloxy Pulse
6.1 Mounting the Aloxy Pulse to an industrial asset
The Aloxy Pulse is only intended for fixed installations and NOT for portable use. Always follow EN-IEC
60079-14, local regulations and local codes of practice when using the Aloxy Pulse.
The Aloxy Pulse can be attached to any (industrial) asset using a variety of attachment methods such
as bolts, straps, magnets or glue. Following procedure must be followed precisely.
Step 1: Remove the Aloxy pulse device from the mounting bracket.
To remove the Aloxy Pulse device from its mounting bracket, put a screwdriver or similar tool in the
release slot to unlock the Aloxy Pulse device from the mounting bracket. Gently pull the device to the
left side while holding the mounting bracket in position and keeping the screwdriver inserted in the
release slot.