Installation Guide

High-Capacity Emergency Lighting Units
Installation Instructions For Standard,
Remote Capacity And Damp
Location Models
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Do not use outdoors.
2. Do not mount near heaters or hot surfaces.
3. Equipment should be mounted in locations and at heights where it will not readily be subject to tampering by
unauthorized personnel.
4. The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition.
Caution: Halogen cycle lamps may be used in this equipment. Halogen cycle lamps operate at high temperatures. Do not
storeorplaceammablematerialsnearlamp.Toavoidshattering:Donotoperatelampinexcessofratedvoltage.Protect
lamp against abrasion and scratches and against liquids when operating. Dispose of lamp with care.
5. Do not use this equipment for other than its intended purpose.
6.Servicingofthisequipmentshouldbeperformedbyqualiedservicepersonnel.
SAVE THESE INSTRUCTIONS
WARNINGThis product contains chemicals known to the State of California to cause cancer, birth defects and/or other
reproductiveharm.Thoroughlywashhandsafterinstalling,handling,cleaning,orotherwisetouchingthisproduct.
EMERGENCY LIGHTING AND POWER EQUIPMENT FOR USE IN DAMP LOCATIONS
Damp location listed units are suitable for use in:
1. Interior locations subject to moderate degrees of moisture, such as some basements, some barns, some cold-storage
warehouses, and the like.
2.Partiallyprotectedlocationsundercanopies,marquees,roofedopenporchesandthelike.
GENERAL INSTRUCTIONS
This unit is designed for surface mounting on a wall or other sold surface (building support structure, column, etc.). Unit must be
mountedhighenoughtomaximizeilluminatedareaunderanticipatedconditionsofuse.Besuretoallowampleclearancefor
mounting and aiming the lighting heads.
Provideeachunitwithasingleunswitchedpowersupplyfroma120or277VACbranchcircuitusedfornormallightinginthesame
area. The wiring should be permanent installation, using appropriate size wire.
Note:De-energizeACcircuittounitduringinitialinstallation,andduringservicingorrelampingoperations.
PLACING THE UNIT IN SERVICE
1. Loosenthetwocoverretainingscrewsonthesidesoftheunit,rotatetheheadsforclearance,andremovethecoverby
lifting it up and outwards.
2. If lighting heads will be retained in the top mounted position, go to step 3. If lighting heads are to be relocated to side
mounted position, proceed as follows:
a. Snap out the lighting head knockouts on the sides of the unit.
b. Loosen the locking nut that retains the stem for each lighting head.
c. Slide each lighting head out of its present slot.
Note: It is not necessary to disconnect the lighting head leads from the circuit board.
d. Insert the stem of each lighting head into the side opening slots.
e. Tighten the locking nut on each stem so that the lamp heads turn with some resistance.
f.Plugthetopmountedopeningslotswiththeholeplugscontainedinthehardwarepack.
3. Fastenenclosuretoelectricaloutletboxand/orwallsurfaceusingappropriatehardware.
Note:Theenclosurecanbemountedto3˚”,4”octagon,or4”squareelectricalboxes,andtostandard
plasterrings.Largeenclosureshaveadditionalkeyholeslotsforsurfacemounting.A
7
/8”diameter
knockoutisprovidedonthetopandoneachsideoftheenclosureforsurfacewiringconduit.
Fig. 4 Double Harness Lead Connection
LeadCalciumBatteries
6VoltTopView
6VoltPack
6VoltAnd12VoltPack(2Packs)
12VoltIndividual(2Batteries
Fig. 5 Single Harness Lead Connection
Nickel-CadmiumBatteries
Fig. 6 Double Harness Lead Connection
Nickel-CadmiumBatteries
6Volt(1Pack)SmallBattery
6Volt(2Pack)LargeBattery
6Volt(2Pack)SmallBattery
12Volt(4Pack)LargeOrSmallBatteries
Double Sided Tape
Double Sided Tape
Double Sided Tape
Double Sided Tape
LM Series
Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com
Copyright
©
HubbellLighting,Inc.,AllRightsReserved•Specicationssubjecttochangewithoutnotice.•PrintedinU.S.A. 0603225 F 9/08

Summary of content (2 pages)