Installation Guide

INSTALLATION INSTRUCTIONS
WALL MOUNT (BACK POWER FEED)
CEILING (TOP) MOUNT
93029219
NOTE:LTmodelsmaybewall
mountedusingtheuniversal
mountingpatternineitherthe
unitorexitsignbackplate
(seeinstructionsbelow).
1. Removecenter¾” K.O. in
selected back plate.
2. Removeappropriatebackplate
K.O.sforelectricalboxscrews.
3. Feedwiresthroughcenter
K.O.andmountbackplateto
electricalbox.
4. Ifmountingbytheexitsignback
plate,routeutilitywiringas
shownforfinalconnectioninside
theunithousing.
CAUTION:IftheLTmodelis
mountedtotheelectricalbox
fromtheexitsignbackplate,
theemergencylightingunitmust
bemechanicallysecuredtothewallusing
thekeyholeK.O.s
providedinthebackplate.
ELECTRICAL CONNECTIONS (ALL MODELS)
93029213
1. Feedbuildingwiresthroughthreadednipplein
ceilingmountbaseplateandaffixtheplateto
theelectricalboxusingscrewsprovidedwithbox.
2. Attachunitmountingbrackettoscrewstudsin
baseplateusingtwoscrewsprovided.
3. Remove¾”K.O.inunitbackplatetopflange
and4appropriateK.O.sinunitbackplate
mountingpattern.
CAUTION:Makesurethethreaded
nipple(usedasthewiringchannel)
extendsfromthebaseplatethroughthe
¾”holeintheunitbackplatetopflange.
4. Placeunitbackplateontoscrewstudsin
bracketassemblyandsecurewith#8
lockinghardwareprovided.
1. Attachunithousingtobackplate
byplastichingestrapsprovided.
93029209
2. Connectbuildingwirestotransformerleads.
•Blackandwhitewiresfor120V(capunusedlead)
•Redandwhirewiresfor277V(capunusedlead)
•Makepropergroundconnection
3. Connectredcircuit board
leadto(+)batteryterminal.
4. Connectremotelightingloadto
yellow(–)andblue(+,fused)
pigtailleadsprovided(remote
capacitymodelsonly).
5. Fire Alarm Panel Interface Option (-FAP)
Connectthetwovioletpigtailleadsfrom
thealarmmoduletoappropriate24volt
ACorDCfirealarmpanelwires.Wiring
connectionsmaybemadeinsidetheunit
housingorwithintheelectricalbox.
REMOTE CAPACITY MODEL JUMPER SETTING
LT_ _ _3 Models only
Remotecapacitymodelsprovidesufficientbatterycapacitytooperate
oneadditional5wattremotelightingfixture.Remotecapacitymodels
withtheSpectron®optionareshippedfromthefactorywithaload
sensingjumperprovidedasshowninposition“A”oftheadjacent
illustration.Inthisposition,theSpectrondiagnosticcircuitrycansense
afailureinanyoftheunit’sthreeconnectedlamps(twointegraland
oneremote).
IMPORTANT
Ifthethird(remote)lightingheadisnottobeconnected(forthe
purposeofextendedruntime
orotherreasons),theloadsensingjumpermust
bereinstalledasshowninPosition“B”toprevent
afalselampfailureindication.
Pos. “A”
Pos. “B”
IMPORTANT:Forceilingmounted
applications,twogroundingpigtail
leadsareprovided.Bothgroundingpig
tailsmustbeproperlyconnectedtothe
buildingutilitygroundforsafetyreasons.
1. Removesafetytabs
tofreebackplate
retainerclips.
2. Disengagedetentsonbottom
edgeofbackplateand
pressbothretainerclipsinward
toremovebackplate.
3. Placedoublefacestencil
assemblyontobackside
ofexitframeandsnap
intoplace.
Double Face Applications
93029349
93029220
continued...