Technical data

5 Installation BECKHOFF Drive Technology
38 Version : 4.5 AX5000
5.2.3.2 Connection example - wiring in series without AX Bridge
Wire the relevant connections using individual cables.
CAUTION
Hazard to inviduals and equipment
Please ensure that the final supply network connection cable is
adequately dimensioned. The dimensioning depends on the total rated
current and must comply with EN60204-1.
To establish a DC link system wire the X02 connections with a suitable
cable. Voltages up to 890 V may be present.
The connectors are designed for a maximum current of 41 A and a
maximum conductor cross-section of 6 mm².
Avoid phase reversal between the devices!
The supply connection is established as described in sections 5.2.1 and 5.2.2.