Another Innovation From Dual-Lite S p e c t r o n ® Continuous Power Compatibility Confidence lsn L i f e S a f e t y N e t w o r k Central Inverter System
S p e c t r o n ® lsn L i f e S a f e t y N e t w o r k The Life Safety Network The Spectron LSN Life Safety Network is designed to provide: ● ● ● ● ● ● ● ● ● ● A simplified system approach to emergency lighting and power “ No break” power P ulse width modulated technology 1 00% load compatibility M aximized reliability R educed maintenance expense E nhanced security I mproved building aesthetics M inimized space requirements C ommunications capability Most importantly, it delive
Spectron LSN - A Major Advance In Life Safety PWM Technology Pulse width modulated (PWM) inverter control is designed to produce the output wave form by switching battery current at a high-frequency rate. The primary circuit of the inverter is made up of four Insulated Gate Bipolar Transistors (IGBT). IGBTs provide the multiple benefits of compactness, high efficiency, low maintenance and long equipment life, as well as maximum adaptability and control.
S p e c t r o n ® lsn L i f e S a f e t y N e t w o r k Design Excellence Inverter Control Board DC Input AC Input/Output Input EMI/RFI Filter Input and Battery Circuit Breakers Control Panel Optional Output Circuit Breakers Air Filters Plus... Cost Efficiency When all factors are considered, including equipment, installation, operating and maintenance costs, Spectron LSN becomes the clear choice to minimize a facility’s total expense for providing life safety power and lighting.
Control Panel LED Status Indicators Display Functions AC-On - AC power is present at output terminals Ready - Unit is ready for emergency operation Emergency Power - Unit is operating on battery power Charging - Unit battery is being charged Alarm - Operation outside of pre-programmed operating parameters detected Display Readout ● Large, easy-to-read characters ●2 -line x 40-character LCD display ●P rovides continuous scrolling of 20 metered functions Control Keys Enter Key (ENT) Allows users t
S p e c t r o n ® lsn L i f e S a f e t y N e t w o r k System Features and Design System Operations AC Utility Input Solid-State Transfer Switch Energy Storage Transformer Filter Control Circuits and Utility Switch Microprocessor Pulse Width Modulated Inverter Battery Charger • A solid-state charger transforms the incoming utility voltage into a regulated DC supply voltage to charge the batteries.
Unit Specifications KVA/KW Rating 1.0K Power Factor Rating 2.0K 2.7K 3.7K 4.8K 5.5K 6.6K 8.3K 10.0K 12.5K 15.0K 17.5K .8 lead to .8 lead to .8 lead to .8 lead to .8 lead to .8 lead to .8 lead to .8 lead to .8 lead to .8 lead to .8 lead to .8 lead to .75 lag .75 lag .75 lag .75 lag .75 lag .75 lag .75 lag .75 lag .75 lag .75 lag .75 lag .
S p e c t r o n ® lsn L i f e S a f e t y N e t w o r k Options Batteries Note: Batteries for all Spectron LSN inverter systems are shipped separately. Batteries must be installed and energized within 90 days of shipment or warranty is void. Spectron LSN’s batteries provide sufficient power to maintain the output voltage of the inverter for a minimum of 90 minutes. All batteries are enclosed in lockable cabinets. Adequate space is provided to ensure easy routine maintenance.
Options Communication Options Fax Modem Option (FAX) The Computer Fax Modem is an option that automatically notifies the user of system test results and alarm conditions. This is accomplished by sending a detailed fax to up to six preprogrammed phone numbers. Fax Modem can establish communication via RS232 to perform any system function. The Fax Modem Option is comprised of a single board computer with factory-installed software, modem card and associated cables.
S p e c t r o n ® lsn L i f e S a f e t y N e t w o r k Service and Support Field Support During or after installation, our Systems Service Department is available to provide expert assistance. Our service representatives are available to answer customers’ questions or solve their problems. Toll-Free Number A toll-free phone has been set up for Spectron LSN service questions.
Ordering Guide How To Develop A Spectron LSN System Control Number The Spectron LSN system control number provides a description of the emergency lighting power system through a meaningful shorthand. Follow the six simple steps outlined below to specify a Dual-Lite Spectron LSN System.
S p e c t r o n ® lsn L i f e S a f e t y N e t w o r k Dual-Lite ● www.dual-lite.com A Hubbell Lighting Inc. brand with representatives’ offices in principal cities throughout North America. Copyright© Dual-Lite, All Rights Reserved - Specifications subject to change without notice. Printed in U.S.A.