Use and Care Manual

dIXEL
Operating Manual
1592020160
1592020160 XR06CX GB r1.2 07.11.07.doc XR06CX 3/3
Mounting: panel mounting in a 71x29mm panel cut-out
Protection: IP20; Frontal protection: IP65
Connections: Screw terminal block 2,5 mm
2
wiring.
Power supply: according to the model 230Vac ±10%, 50/60Hz --- 110Vac ±10%, 50/60Hz
Power absorption: 3.5VA max
Display: 2 digits, red LED, 14,2 mm high; Inputs: Up to 2 NTC.
Digital input: free voltage contact
Relay outputs: compressor SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac or 20(8)A 250Vac
defrost: SPDT 8(3) A, 250Vac
fan: SPST 8(3) A, 250Vac or SPST 5(2) A
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B; Pollution grade: 2;Software class: A.;
Rated impulsive voltage: 2500V; Overvoltage Category: II
Operating temperature: 0÷60 °C;Storage temperature: -25÷60 °C.
Relative humidity: 20÷85% (no condensing)
Measuring and regulation range: NTC -40÷110°C;
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,1 °C ±1 digit
15. CONNECTIONS
15.1 XR06CX – 20+8+5A OR 16+8+5A – 110VAC OR 230VAC
NOTE: The compressor relay is 20(8)A or 16(6)A depending on the model.
NOTE: Connect the 120Vac power supply to 4-5
15.2 XR06CX -- 8+8+8A -- 110VAC OR 230VAC
NOTE: Connect the 120Vac power supply to 6-7
16. DEFAULT SETTING VALUES
LAB
EL
DESCRIPTION RANGE DEFAULT
REGULATION
Hy
Differential 0.1 ÷ 25°C/1 ÷ 45°F 2.0°C / 4 °F
LS
Minimum Set Point -55°C÷SET/-67°F÷SET
-55 °C /-
55°F
US
Maximum Set Point SET÷99°C/ SET÷99°F
99 °C /
99°F
ot
First probe calibration -9.9÷9.9°C/-17÷17°F 0.0
P2
Second probe presence n – Y y
oE
Second probe calibration -9.9÷9.9°C/-17÷17°F 0.0
od
Outputs activation delay at start up 0 ÷ 99 min 0
AC
Anti-short cycle delay 0 ÷ 50 min 1
Cy
Compressor ON time faulty probe 0 ÷ 99 min 15
Cn
Compressor OFF time faulty probe 0 ÷ 99 min 30
DISPLAY
CF
Measurement units °C - °F °C / °F
rE
Resolution (only for °C) dE – in dE
Ld
Default Display P1 - P2 - SP P1
dy
Display delay 0 ÷ 15 min 0
DEFROST
td
Defrost type EL – in EL
dE
Defrost termination temperature
-55÷50°C/-67÷99°F
8.0 °C / 46
°F
id
Interval between defrost cycles 0 ÷ 99 hours 6
Md
Maximum length for defrost 0 ÷ 99 min. 30
dd
Start defrost delay 0 ÷ 99 min. 0
dF
Display during defrost rt – in – SP – dF
it
dt
Drip time 0 ÷ 99 min 0
dP
Defrost at power-on y - n
n
FANS
FC
Fans operating mode cn – on – cY – oY on
Fd
Fans delay after defrost 0 ÷ 99 min 10
FS
Fans stop temperature -55÷50°C/-67÷99°F
2.0 °C / 36
°F
ALARMS
AU
Maximum temperature alarm
ALL÷99°C / ALL÷99°F
99 °C / 99
°F
AL
Minimum temperature alarm
-55°C÷ALU/-
67°F÷ALU
-55 °C / -
55 °F
Ad
Temperature alarm delay 0 ÷ 99 min 15
dA
Exclusion of temperature alarm at
startup
0 ÷ 99 min 90
DIGITAL INPUT
iP
Digital input polarity cL – oP cL
iF
Digital input configuration
EA – bA – do – dF – Au
– Hc
EA
di
Digital input delay 0 ÷ 99 min 5
dC
Compressor and fan status when open
door
no /Fn / cP / Fc FC
rd
Regulation with door open n - Y y
OTHER
d1
Thermostat probe display Read Only - - -
d2
Evaporator probe display Read Only - - -
Pt
Parameter code table Read Only - - -
rL
Firmware release Read Only - - -