Use and Care Manual
Table Of Contents
17
www.factorybuysdirect.com
200273-01C
INSTALLATION
Figure 15 - Equipment Shuto Valve
CHECKING GAS CONNECTIONS
Open
Closed
Equipment
Shuto Valve
WARNING: Never use an open
ame to check for a leak. Apply
a noncorrosive leak detection
uid to all joints. If bubbles form,
there is a leak. Correct all leaks
at once.
Control Valve
Location
Equipment
Shuto Valve
External Regulator
Propane
Supply Tank
Figure 16 - Checking Gas Joints for
Propane Gas
Figure 17 - Checking Gas Joints for
Natural Gas
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect heater with its appliance main
gas valve (control valve) and equipment
shuto valve from gas supply piping sys-
tem. Pressures in excess of 1/2 PSIG will
damage heater regulator.
2. Cap o open end of gas pipe where equip-
ment shuto valve was connected.
3. Pressurize supply piping system by either
opening propane supply tank valve for
propane gas or opening main gas valve
located on or near gas meter for natural
gas or using compressed air.
4. Check all joints of gas supply piping sys-
tem. Apply noncorrosive leak detection
uid to all joints. If bubbles form, there
may be a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shuto
valve to gas supply. Check reconnected
ttings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shuto valve (see Fig-
ure 15).
2. Pressurize supply piping system by either
opening propane supply tank valve for
propane gas or opening main gas valve
located on or near gas meter for natural
gas or using compressed air.
3. Check all joints from gas meter to equip-
ment shutoff valve for natural gas or
propane supply to equipment shuto valve
for propane (see Figure 16 or 17). Apply
a noncorrosive leak detection uid to all
joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Control Valve
Location
Equipment Shuto Valve
External Regulator
Supplied by Gas
Supplier
Gas
Meter