Installation Guide
www.factorybuysdirect.com
200254-01A10
INSTALLATION
CHECKING GAS CONNECTIONS
 WARNING: Test all gas piping 
and connections for leaks after 
installing or servicing. Correct 
all leaks immediately.
 WARNING: Never  use an 
open ame to check for a leak. 
Apply a noncorrosive leak detec-
tion uid  to all joints. Bubbles 
forming show a leak. Correct all 
leaks immediately.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5kPa)
1.  Disconnect heater with its appliance main 
gas valve (control valve) and equipment 
shutoff valve from gas supply piping sys-
tem. Pressures in excess of 1/2 PSIG will 
damage heater regulator.
2.  Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3.  Pressurize supply piping system by either 
using compressed air or opening gas sup-
ply tank valve.
4.  Check all joints of gas supply piping sys-
tem. Apply a noncorrosive leak detection 
uid to gas joints. Bubbles forming show 
a leak.
5.  Correct all leaks immediately.
6.  Reconnect  appliance  and  equipment 
shutoff valve to gas supply. Check recon-
nected ttings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1.  Close equipment shutoff valve (see Fig-
ure 9).
2.  Pressure supply piping system by either 
using  compressed  air  or  opening  gas 
supply tank valve.
3  Check all joints from gas meter to equip-
ment shutoff valve (see Figure 10). Apply 
a noncorrosive leak detection uid to gas 
joints.  If  bubbles  form,  there  may  be  a 
leak.
4.  Correct all leaks immediately.
Figure 9 - Equipment Shutoff Valve
Open
Closed
Equipment 
Shutoff Valve
Figure 10 - Checking Gas Joints
Equipment Shutoff Valve
Gas Meter