Installation guide

Burn, scald hazard. Do not attempt to start the
burner when excess oil has accumulated, when
the unit is full of vapor, or when the combustion
chamber is very hot.
You or your installer must follow these instructions
carefully.
Adjust Operating Controls: Use the following settings
for first adjustment:
High Limit:
Baseboard and Convectors 200°F
Standing Radiators 180°F
Low Limit (when used) 1400 ( increase if hotter domestic
water is required, low limit set point must be at least 20°F less
than high limit set point)
Locate thermostat five feet above the floor on inside wall.
Locate thermostat to sense average room temperature,
avoid the
Behind
doors
Corners &
alcoves
Concealed pipes
Fireplace
TV sets
Radios
Lamps
Direct sunlight
Kitchens
Concealed pipes
or ducts
Stairwells drafts
Doors drafts
Unheated room
on other side of
wall
When temperature on thermostat is set above indicated
thermostat temperature, boiler's burner should start. Verify
that when room temperature reaches selected temperature
setting, thermostat should turn boiler's burner off, and once
room temperature falls few degrees boiler starts operating
again.
Do not start burner unless all cleanout doors are
secured in place.
Adjust Thermostat Heat Anticipator To: 0.2
Amps
Check Thermostat Operation:
Follow instructions included with your thermostat.