All Air from Outdoors: Confined space shall
be provided with two permanent openings, one
commencing within 12 inches of top and commencing
within 12 inches of bottom of enclosure. Openings
shall communicate directly, or by ducts, with outdoors
or spaces (crawl or attic) that freely communicate with
outdoors.
1. When directly communicating with outdoors, each
opening shall have minimum free area of one
square inch per 4,000 Btu per hour of total input
rating of all equipment in the enclosure.
2. When communicating with outdoors through
vertical ducts, each opening shall have minimum
free area of one square inch per 4,000 Btu per
hour of total input rating of all equipment in the
enclosure.
3. When communicating with outdoors through
horizontal ducts, each opening shall have
minimum free area of one square inch per 2,000
Btu per hour of total input rating of all equipment
in the enclosure.
4. When ducts are used, they shall be of same cross
sectional area as free area of openings to which
they connect. Minimum dimension of rectangular
air ducts shall be not less than three inches.
Figure 5 = Fresh Air Duct Capacities For Ducts Supplying Fresh Air To Boiler In
Tightly Constructed Houses
12" CL£A£
3 V2"x 12" 144,000 36,000 i08,000
8" x 8" 256,000 64,000 192,000
8" x 12" 384,000 96,000 288,000
8" x 16" 512,000 128,000 384,000