INSTALLATION MANUAL Q90 50-100 GAS-FIRED, DIRECT VENT, CONDENSING, HOT WATER BOILER DUNKIRK BOILERS 85 Middle Rd. Dunkirk, NY 14048 www.dunkirk.com MEMBER: The Hydronics Institute An ISO 9001-2000 Certified Company P/N# 14683301, Rev. 3.
Owner s Manual Model No. Q90-50 Q90-75 Q90-100 These instructions must be affixed on or adjacent to the boiler. WARNING Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, or the gas supplier. CAUTION Read all instructions carefully before starting the installation. Save this manual for reference.
TABLE OF CONTENTS TABLE OF CONTENTS INTRODUCTION .............................................................................. 4 BOILER RATINGS AND CAPACITIES .................................................................................... 7 BOILERS FOR USE AT HIGH ALTITUDE ............................................................................... 8 RULES FOR SAFE INSTALLATION AND OPERATION ...................................................... 10 BEFORE INSTALLING THE BOILER .....................
TABLE OF CONTENTS H. draft inducer...................................................................................................................... 37 I. circulator pump.................................................................................................................. 37 J. drain valve......................................................................................................................... 37 K. A.S.M.E. rated pressure relief valve..........................................
INTRODUCTION This appliance is a gas-fired direct vent hot water boiler with cast aluminum boiler sections. A revolutionary cast aluminum heat exchanger means better heat transfer and thermal storage than similarly sized cast iron boilers, which results in higher efficiency. The heating system water absorbs large amounts of heat from the cast aluminum heat exchanger, cooling the flue gases and causing condensation.
BOILER RATINGS AND CAPACITIES TABLE #1 – SEA LEVEL RATINGS – NATURAL AND PROPANE GASES Shipping Input ++ Heating Capacity Net I=B=R Rating Flue Dia. Model *(MBH) *(MBH) *(MBH) Weight (lbs.) 90-50 50 45 39 220 2” CPVC & PVC 90-75 75 68 59 220 2” CPVC & PVC 90-100 100 90 78 220 2” CPVC & PVC * 1 MBH = 1,000 Btuh Btuh = British Thermal Units Per Hour These low pressure gas-fired hot water boilers are design certified by CSA International for use with natural and propane gases.
BOILERS FOR USE AT HIGH ALTITUDE The boilers are factory equipped for operation at altitudes ranging from 0-2,000 feet above sea level. For use of these boilers at altitudes above 2,000 feet above sea level, the gas input ratings (MBH) must be reduced. certified high altitude conversion kit. The change in main burner orifice size results in a 10% reduction of the boiler gas input rating (MBH). The conversion shall be carried out by a manufacturer’s authorized representative, U.S.A.
BOILERS FOR USE AT HIGH ALTITUDE TABLE #1C – MODEL-75 NATURAL GAS HIGH ALTITUDE RATINGS Elevation (Feet) 0-2,000 3,000 4,000 5,000 6,000 7,000 7,500 Nominal Input (MBH) 75.0 70.0 69.0 68.0 63.5 58.0 56.5 Heat Capacity (MBH) 68.0 63.0 62.1 61.2 57.2 52.2 50.9 NET I=B=R Rating (MBH) 58.9 54.6 53.8 53.0 49.6 45.2 44.1 .0760 .0760 .0760 .0760 .0760 .0760 .0760 GAS Orifice Drill Size “Manifold Pressure 2.5 2.7 2.8 3.0 2.8 2.6 2.3 (Inches Water Column)” “Pressure Switch Set-point 1.35 1.35 1.35 1.35 1.35 1.35 1.
RULES FOR SAFE INSTALLATION AND OPERATION l. Read the entire installation manual before beginning the installation. Failure to follow these rules for safe installation and operation and these instructions could cause a malfunction of the boiler and result in death, serious bodily injury, and/or property damage. 2. Check all applicable state and local building codes and utility company requirements before installation. The installation must conform with these requirements in their entirety.
BEFORE INSTALLING THE BOILER Continued The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1 - latest revision. Installers - Follow local regulations with respect to installation of CO (Carbon Monoxide) Detectors. Follow maintenance recommendations in this manual.
BEFORE INSTALLING THE BOILER Continued TABLE #2 - BOILER CLEARANCES Unit Combustible Clearance Inch (mm) Accessibility, Cleaning, and Servicing Inch (mm) Top 1 (25.4) 8 (203.2) Left Side 1 (25.4) 24 (609.6) Right Side 8 (203.2) - Base 1 (25.4) - Front 0 (0) 24 (609.6) Back Intake/Vent Piping 1 (25.4) 0 (0) - Near Boiler Hot Water Piping 1 (25.4) - All distances measured from the cabinet of the boiler.
BEFORE INSTALLING THE BOILER Continued ! CAUTION ! KEEP BOILER AREA CLEAN OF DEBRIS AND FREE OF FLAMABLE AND COMBUSTIBLE MATERIALS, VAPORS AND LIQUIDS ! WARNING ! When vent pipe is exposed to temperatures below freezing, such as when it passes through an unheated space or when a chimney is used as a raceway, vent pipe must be insulated with 1/2” Armaflex or equivalent. In extreme cold climate areas, use ¾” Armaflex or equivalent. Combustion air must be clean outdoor air.
BEFORE INSTALLING THE BOILER Continued G. FOUNDATION REQUIREMENTS 4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliances will operate continuously. Boiler must be placed on level surface. Boiler is NOT to be installed on carpeting. NOTE: 1. If boiler is not level condensate drain lines will not function properly. Adjustable feet are located on the boiler to make up for minor surface irregularities or tilt. 2.
NEAR BOILER PIPING ! CAUTION ! Copper supply and return piping. must NOT be installed directly into aluminum boiler section casings due to galvanic corrosion between dissimilar metals. Iron or steel bushings or pipe nipples should be used between copper system piping and boiler to make final connection to boiler. Also, the use of dielectric unions is acceptable. The packaged boiler is furnished with iron piping in the front boiler section for the supply and return connections. boiler.
SUPPLY AND RETURN LINES Figure #2 SINGLE ZONE BOILER PIPING 16
SUPPLY AND RETURN LINES Figure #3 MULTI ZONE BOILER PIPING WITH ZONE VALVES 17
SUPPLY AND RETURN LINES Figure #4 MULTI ZONE BOILER PIPING WITH CIRCULATORS NOTE: When zoning with circulators, the furnished circulator pump should be used as one of the zone pumps. Each stripped end of the electrical wires for the circulator pump inside the junction box should be taped or wire nutted to prevent short circuits. Unplug the circulator pump wiring at the integrated boiler control.
SUPPLY AND RETURN LINES Figure #5 SINGLE ZONE BOILER PIPING B. PRESSURE RELIEF VALVE Size expansion tank accordingly. Consult expansion tank manufacturer for proper sizing information. Connect properly sized expansion tank (not furnished) as shown in Figure 6 for diaphragm type expansion tank and Figure 7 for conventional closed type expansion tanks. For diaphragm type expansion tanks, adjust the tank air pressure to match the system fill pressure.
SUPPLY AND RETURN LINES Figure #6 DIAPHRAGM TYPE EXPANSION TANK PIPING 20
SUPPLY AND RETURN LINES Figure #7 CONVENTIONAL (closed type) EXPANSION TANK PIPING 21
SUPPLY AND RETURN LINES Figure #8 CONDENSATE - DRAIN PIPING D. CONDENSATE DRAIN PIPING The condensate trap is built into the boiler, an external trap is not required and should NOT be used. Provide ½” PVC condensate drain and fittings. Condensate drain to be pitched down to floor drain at a minimum of ¼” per foot. Install furnished ½” PVC tee to overflow fitting as shown in Figure 8.
SUPPLY AND RETURN LINES E. FILLING CONDENSATE TRAP WITH WATER ON THE INITIAL START UP THE CONDEN SATE TRAP MUST BE MANUALLY FILLED WITH WATER The following are the steps required to initially fill F.
COMBUSTION AIR AND VENT PIPE In Canada construct all combustion air and vent pipes for this unit of CSA or ULC certified schedule-40 CPVC, schedule-40 PVC, PVC-DWV or ABS-DWV pipe and pipe cement. SDR pipe is NOT approved in Canada. 3. PVC. If any elbows are employed within the Combustion air and vent piping connections first 5 feet of vent, they must be CPVC too. on boiler are sized for 2” pipe.
COMBUSTION AIR AND VENT PIPE 6. Consideration for the following should be used when determining an appropriate location for termination of combustion air and vent piping. boiler to shut down if the vent becomes obstructed. • Under certain conditions, flue gas will condense, forming moisture, and may be corrosive. In such cases, steps should be taken to prevent building materials at the vent from being damaged by exhaust of flue gas. • Comply with all clearances required as stated in paragraph 7.
COMBUSTION AIR AND VENT PIPE Figure #10 SIDEWALL VENT/INTAKE TERMINATIONS 26
COMBUSTION AIR AND VENT PIPE Figure #11 COMBUSTION AIR AND VENT PIPING 27
COMBUSTION AIR AND VENT PIPE B. INSTALLATION 1. Attach combustion air intake piping to supplied Fernco 2” coupling on mixer. Attach vent piping to furnished 2” CPVC vent tee on draft inducer outlet. NOTE: All pipe joints are to be water tight. 2. 3. 4. 5. 6. 8. Working from the boiler to the outside, cut pipe to required length(s). Deburr inside and outside of pipe. Chamfer outside edge of pipe for better distribution of primer and cement. Clean and dry all surfaces to be joined.
GAS SUPPLY PIPING B. CONNECTING THE GAS PIPING Refer to Figure 12 for the general layout at 6. Install a manual shutoff valve in the vertical the boiler. It shows the basic fittings you will pipe about 5 feet above floor. need. The gas line enters the boiler from the 7. Tighten all joints securely. right side jacket panel. The boiler may receive 8. Propane gas connections should only be the gas supply pipe through the left side, or made by a licensed propane installer.
GAS SUPPLY PIPING Figure #12 GAS PIPING ELECTRICAL WIRING ! WARNING ! TURN OFF ELECTRICAL POWER AT FUSE BOX BEFORE MAKING ANY LINE VOLTAGE CONNECTIONS. FOLLOW LOCAL ELECTRICAL CODES. All electrical work must conform to local codes as well as the National Electrical Code, ANSI/NFPA70, latest revision. In Canada, electrical wiring shall comply with the Canadian Electrical Codes, CSAC22.1 and .2 A.
ELECTRICAL WIRING to the white screw on the service switch. Connect the green (ground) lead from the power supply to the ground (green) screw on the service switch. The receptacle on the service switch is always powered regardless of whether the switch is on or off, and could be used as a power supply for an external condensate pump if one is used.
ELECTRICAL WIRING Figure #13 FIELD WIRING CONNECTIONS 32
ELECTRICAL WIRING Figure #14 (D) SCHEMATIC WIRING DIAGRAM If any of the original wire as supplied with this appliance must be replaced, it must be replaced with type 150°C Thermoplastic wire or its equivalent 33
ELECTRICAL WIRING Figure #15 (E) LADDER WIRING DIAGRAM 34
CONTROLS AND ACCESSORIES This section provides a brief description of the key controls and accessories found in this boiler. See the Troubleshooting section of the Service Hints chapter of this installation manual for detailed sequences of operation and troubleshooting procedures. See the Repair Parts chapter of this manual for locations of all control components and accessories described. A.
CONTROLS AND ACCESSORIES F. CASTING TEMPERATURE SAFETY SWITCH before being discharged through the vent pipIn the event of lack of or loss of water in the ing to the outdoors. See applicable sections for boiler, the Casting Temperature Safety Switch proper sizing and installation of combustion air (300 °F setpoint) installed on the top of the and vent piping in this manual. aluminum boiler section shuts off the boiler by shutting off power to the Integrated Boiler I.
CONTROLS AND ACCESSORIES K. A.S.M.E. RATED PRESSURE RELIEF VALVE event of blocked flueways, enough air will Each boiler must have a properly sized and not be available to support combustion, and installed American Society of Mechanical the S9301 Integrated Boiler Control (IBC) will Engineers rated pressure relief valve. Water lockout due to loss of adequate air flow (after expands as it is heated by the burner/boiler 3 trials for ignition). The “PURGE” diagnostic sections.
START - UP c. In older system, obviously discolored, murky, or dirty water, or a pH reading below 7, are indications that the system should be cleaned. d. A pH reading between 7 and 8 is preferred. 3. Antifreeze if needed, must be of a type specifically designed for use in closed hydronic heating systems and with aluminum. a. Choice and use of antifreeze must be in accordance with local plumbing codes. b Only INTERCOOL NFP-50 is approved for use.
START - UP 4. Open the expansion tank service valve and the expansion tank when the boiler is placed the tank vent. Fill the tank to the proper level in operation. and close the tank vent. Remove the handle 6. Inspect piping system. Repair any leaks from the expansion tank service valve so the immediately. homeowner doesn’t accidentally close it. NOTE: 5. Open all service valves. Any air remaining DO NOT use stop leak compounds.
CHECK OUT PROCEDURE AND ADJUSTMENT Figure #16 INDICATOR LAMPS A. VERIFY PROPER SEQUENCE OF OPERATION The sequence can be followed via the diagnostic indicator lamps on the Honeywell S9301A integrated boiler control in Figure 16. This is the normal sequence of operation. A more detailed sequence of operation containing potential faults can be found in the service hints section. SEQUENCE OF OPERATION “DIAGNOSTIC INDICATOR LAMPS” “Power ON, boiler standing by.
CHECK OUT PROCEDURE AND ADJUSTMENT SEQUENCE OF OPERATION “DIAGNOSTIC INDICATOR LAMPS” After pre purge, Lamp B goes out and Lamp C illuminates, indicating the hot surface igniter is powered for the 20 second igniter warm-up period. The bright yellow orange glow of the hot surface igniter can be observed through the observation port in the f A. B. C. D. E. After igniter warm-up, the gas valve is energized, and opens on the normal firing rate regulator (2.5” w.c.
CHECK OUT PROCEDURE AND ADJUSTMENT F. TEST HIGH LIMIT CONTROL AND ADJUST While burner is operating, move indicator on high limit control below actual boiler water temperature. Burner should go off while circulator continues to operate. Raise limit setting above boiler water temperature and burner should reignite after pre purge and igniter warm-up period. Set the high limit control to the design temperature requirements of the system. Maximum high limit setting is 200°F. Minimum high limit setting is 100°F.
CHECK OUT PROCEDURE AND ADJUSTMENT Figure #17 MANIFOLD PRESSURE MEASUREMENT DETAIL THE FOLLOWING STEPS AND DIAGRAM INDICATE T H E L O C AT I O N O F THE CONNECTION POINTS REQUIRED TO MEASURE THE MANIFOLD PRESSURE. THE MANIFOLD PRESSURE MAY BE MEASURED USING A U-TUBE MANOMTERE OR A DIFFERENTILA PRESSURE GAUGE. THE DIAGRAM SHOWS THE CONNECTION OF BOTH MEASURING DEVICES BUT ONLY ONE DEVICE IS REQUIRED TO MEASURE THE MANIFOLD PRESSURE. © REMOVE THE PLUG.
CHECK OUT PROCEDURE AND ADJUSTMENT I. Remove regulator cover screw on top of gas valve, and insert an appropriate screwdriver into adjustment screw. II. Turn adjustment screw clockwise to increase input rate, or counter clockwise to decrease input rate. III. Replace cover screw, or cover hole temporarily with your finger to check new manifold pressure setting. Do not set manifold pressure lower than 2.0 inches w.c. or higher than 3.0 inches w.c. when adjusting input rate. IV.
INSTALLATION AND CHECK-OUT CERTIFICATE Boiler Model Serial # Date Installed___________ Measured BTU/HR input____________ Installation instructions have been followed Checkout procedure and adjustments performed Maintenance and Service issues reviewed with owner/ maintenance person Installation booklet affixed on or adjacent to boiler Installer (Company) Address Phone Installer’s Name Signature 45
MAINTENANCE AND CLEANING Maintenance as outlined below can be performed by the owner unless otherwise noted. The acidic nature of flue gasses condensing on the aluminum boiler sections will cause the formation of aluminum oxide. This oxide formation is normal, is generally uniform throughout the boiler sections, and represents a negligible mass of aluminum that is consumed by oxidation during the life of the boiler.
MAINTENANCE AND CLEANING C. MONTHLY DURING HEATING SEASON 1. Remove jacket front and top panels and check for piping leaks around relief valve and other fittings. If found, contact a qualified service agency to repair. DO NOT use stop leak compounds. 2. Test relief valve. Refer to valve manufacturers instructions packaged with relief valve. 2. If heating system is to remain out of service during freezing weather, and does not contain antifreeze, drain system completely.
MAINTENANCE AND CLEANING c. Remove air baffle from 1% z” x 2” flexible cou- l. Connect: pling and clean air baffle if necessary. Refer • gas line to gas valve to repair parts diagram, mixer and pressure • condensate drain line to boiler switch assembly. • pressure switch hose to gas valve • air by-pass to mixer d. Confirm that manual gas valve is closed and • 1 ½” x 2” flexible coupling to air inlet and disconnect gas line to gas valve at union. Disconnect wires to gas valve. and igniter.
MAINTENANCE AND CLEANING d. Reinstall and connect the condensate trap, using the hose clamps to secure the various condensate lines to their fittings. e. Follow the instructions under “NEAR BOILER PIPING” for”filling condensate trap with water” 4. Inspection of the flue connector requires the following steps (Refer to the repair parts diagram.) a. Loosen the clamp on the draft inducer end of the 2” flexible coupling that connects the vent tee to the draft inducer.
DETAILED SEQUENCE OF OPERATION SERVICE HINTS 50
DETAILED SEQUENCE OF OPERATION 51
DETAILED SEQUENCE OF OPERATION END OF NORMAL SEQUENCE OF OPERATION 52
TROUBLESHOOTING ! ! WARNING FIRE, EXPLOSION OR SHOCK HAZARD MAY CAUSE PROPERTY DAMAGE, SEVERE INJURY OR DEATH. DO NOT ATTEMPT TO MODIFY THE PHYSICAL OR ELECTRICAL CHARACTERISTICS OF THIS BOILER IN ANY WAY. ! IMPORTANT ! 1. IN A RESET FROM LOCKOUT CONDITION, ALL ELECTRICAL METER READINGS AT THE GAS CONTROL VALVE (24 VAC) MUST BE TAKEN WITHIN THE TRIAL FOR IGNITION PERIOD. 2. IF ANY COMPONENT DOES NOT FUNCTION PROPERLY, MAKE SURE IT IS CORRECTLY INSTALLED AND WIRED BEFORE REPLACING IT. 3.
TROUBLESHOOTING SYSTEM STATUS THE INDICATOR LIGHTS TRACK THE OPERATING SEQUENCE. IF THE SYSTEM LOCKS OUT, THE LIGHTS INDICATE THE POINT IN THE SEQUENCE OF OPERATION WHERE LOCKOUT OCCURS. IF THIS TABLE DOES NOT READILY PROVIDE THE REASON FOR BOILER MALFUNCTION OR NON-OPERATION, REFER LIGHT STATUS ON IBC IS ENERGIZED THROUGH 24 VOLT TRANSFORMER. POWER OFF IBC IS NOT ENERGIZED. BLINKING ON INDICATES IBC RECEIVES MORE THAN 40 VAC IBC IS ENERGIZING THE DRAFT INDUCER AND AIR FLOW IS PROVEN.
TROUBLESHOOTING TROUBLESHOOTING CHART 1 ! WARNING ! �� ������������������������������� ����������������������� ������� ��� ELECTRICAL SHOCK HAZARD MAY CAUSE SERIOUS INJURY OR DEATH. THE FOLLOWING PROCEDURES MAY EXPOSE YOU TO DANGEROUS LINE VOLTAGE. USE CAUTION TO AVOID TOUCHING LIVE ELECTRICAL CONTACTS. SERVICE MUST BE PERFORMED BY A TRAINED, EXPERIENCED SERVICE TECHNICIAN.
TROUBLESHOOTING TROUBLESHOOTING CHART 2 �� ������� ������������������������������������ ������������������������������������ �� ������������������������������� �� ��������������������������������� ������������������������������������� ������������������������������������ �������������� ���� ����������������������������������� ��������������������������������� ������������������������������������ ����������������� ������ ������������������������������������� ������������������������������������ ��������
TROUBLESHOOTING TROUBLESHOOTING CHART 3 ������� ���� �� ������������� �������������� �� �������������������������� ����������������������� ��� ����������� ��� ��������������������� ����������������������� ������� �� �������������� ���������������� ��������� ��� ��������������� ������ ���������������� ��������� ���� �� ��������������� ��� ������������������ ��������������������� ��������� ���������������� ������������������ ����������������� ����������� �������� ���������������������� �����������
TROUBLESHOOTING TROUBLESHOOTING CHART 4 CHART 3 YES IGNITER/SENSOR WARMS UP AND GLOWS YELLOW/ORANGE DURING 20 SECOND WARM UP NO CHECK FOR 120 VAC BETWEEN TERMINALS 1 AND 2 AT CONNECTOR CN1 ON IBC (DURING IGNITER WARM UP) NO YES YES CHECK FOR 120 VAC AT IGNITER/SENSOR LEADS ON WIRING HARNESS (DURING IGNITER WARM UP) NO YES AFTER 20 SECOND IGNITER WARM UP, GAS VALVE IS ENERGIZED VALVE LIGHT IS ON 2 SECONDS LATER POWER IS REMOVED FROM IGNITER/SENSOR IGNITER LIGHT IS OFF DOES MAIN BURNER LIGHT? REPLACE
TROUBLESHOOTING TROUBLESHOOTING CHART 5 ������� ��� ������� ��� �������������������������� ���������������������������������� ������������������� �������������������� ����������������������������������� ������������������������� �� ������������������������� ���������������������������������������������� ��� ������������������������� ���������������������������������� �������������������������������� ������������������������������ �� ������������������������������������������� �����������������������
TROUBLESHOOTING TROUBLESHOOTING CHART 6 CHART 5 NO #2 CHART 5 NO #3 CHART 5 YES REPLACE GAS CONTROL. YES CHECK GAS ORFICICE SIZE. IS GAS ORIFICE SIZE CORRECT. CHECK REPAIR PARTS LIST FOR CORRECT SIZE. IS GAS ORIFICE CLEAR OF BLOCKAGE. RUNS FOR 25-50 SECONDS, THEN TURNS OFF. CHECK FIRING RATE OF UNIT. IS UNIT FIRING AT THE CORRECT RATE? YES NO DOES THE UNIT USE LP GAS. NO ADJUST RATE AS DESCRIBED IN THE CHECK OUT PROCEDURE AND ADJUSTMENT SECTION OF THE MANUAL.
DIFFERENTIAL AIR PRESSURE SWITCH CHECK C. WHAT IS SYSTEM STATUS? The following steps and diagram indicate the locations of the connection points required to check the differential air pressure. The differential air pressure switch is a safety device which will prevent the boiler from firing if there is an air intake, boiler heat exchanger or vent blockage. Turn off service switch, or lower thermostat setting. Remove vinyl caps from Tee and 4-way connector.
REPAIR PARTS A.
REPAIR PARTS A.
REPAIR PARTS B.
REPAIR PARTS B. CONDENSATE DRAIN TRAP ASSEMBLY KEY # 1 2 3 4 5 6 7 8 DESCRIPTION 59019 ½”IDx1/8” THK VINYL TUBING 57134 ¾” SNAP GRIP CLAMP 62067 ½”ID HOSE TEE 62017 ½”NPTx ½”ID TUBE STRAIGHT ½” PVC COUPLING, SCH 80 ½”´4” PVC NIPPLE, SCH 80 TEE PVC ½”SLIP x ½”SLIP x ½”NPT FEMALE S. S.
REPAIR PARTS C.
REPAIR PARTS C. BOILER BLOCK AND PIPING ASSEMBLY KEY # ITEM NUMBER DESCRIPTION QUANTITY 1 1580006 AIR PURGE VENT 1 2 14693001 ¾” x 1/8” BUSHING 1 3 14693076 ¾” BLACK TEE 1 4 14693040 ¾” x 90º STREET ELBOW 2 5 14607002 ¾” x 6½” NIPPLE 2 6 14622011 ¾” ASME RELIEF VALVE 1 7 14607201 ¾”x 2” NIPPLE 1 8 14695810 ¼”-20 HEX NUT W/SERRATED WASHER HEAD 9 9 14695802 8-32 x 3/16” SOC HD CAP SCREW 2 10 14631000 36T26-42930 CASTING TEMP.
REPAIR PARTS D.
REPAIR PARTS D.
REPAIR PARTS E.