Datasheet

POWER YOU CAN TRUST
Product SpecicationsProduct Specications
Duracell Power Center 5kW
PCS: AC RATINGS
Rated power
Rated voltage
Rated frequency
Rated current
Maximum overcurrent protection
Power factor range
DC ground fault monitoring
[kW]
[V]
[Hz]
[A]
[A]
5.0
240/120 split-phase
60
20.8
60.0
0.8 lead to 0.8 lag
Included
PCS BACKUP POWER RATINGS
Rated output power
Surge rating (6+ battery modules required)
Transfer power interrupt time: to backup / to grid
GENERAL RATINGS
Mounting method
Ambient operating temperature range (recommended)
Relative air humidity, maximum


Protection degree
Galvanic Isolation
Cooling - PCS / Battery
Energy consumption, standby (operating)
Display / EMS communication
[KVA]
[%]
[s]
5.0
120 (30 min), 170 (5 sec)
4.0 / 0.0
CERTIFICATIONS & WARRANTY
EMC
Safety
Utility interface
Warranty / battery performance guarantee
The installed circuit breaker rating is dependent upon the interconnected Duracell Power Center model rating.



1.
2.
3.
FCC Part 15 Class B
UL 9540, UL 1741SA, UL 1973, CSA 22.2 No 107.1, IEEE 1547
CSIP Rule 21, HI Rule 14H
10 year / 70% capacity, pro-rated / 15 year power controls
[°C]
[%]
[%]
[%]
[W]
Wall-mount
0 to 50 (15 to 30)
95 ( non-condensing)
> 85.7
94.5
Type 3R (NEMA), Indoor / Outdoor
Transformer
Fan (thermostat) / convection
8 (30)
LED: battery SOC level, system status / Modbus RS-485
BATTERY MODULE RATINGS
Chemistry
Voltage range

discharge current (recommended)
DC capacity / (usable)
Cycle life
[Vdc]
[Adc]
[kWh]
LiFePO
44.5 to 53.5
74.0 (37.0)
3.55 / (3.37)
>6000 @ 25°C
DC ENERGY STORAGE RATINGS
Maximum battery modules per cabinet
DC capacity (usable), per cabinet
Total maximum continuous PCS
charge / discharge current
Total maximum capacity (1C)

Total maximum energy (1C)

[kWh]
[Adc]
[aH]
[kWh]
4
14.2 (13.5)
100 / 125
887.5
42.6

Power rating 5 kW
Battery capacity 14kWh to 42kWh
DIMENSIONS
D-5kW
D-14kWh-LFP
D-14kWh-LFP D-14kWh-LFP
65 kg / 145 lb 101 kg / 223 lb 99 kg / 218 lbs 99 kg / 218 lbs
782 mm (30.8")
400 mm (15.7")
528 mm (20.8") 572 mm (22.5") 572 mm (22.5") 572 mm (22.5")