Install Manual

16
5.7 PCS DC+ power and breaker assembly wiring
1. Route the PCS DC+ power cable from the PCS through
the cabinet coupling port.
2. Terminate the PCS DC+ cable, referenced
[P+], at the top right busbar terminal of the DC
breaker as shown. Torque to 15 in/lbs.
3. Terminate the DC+ power cables referenced B2 and B3 at
the lower battery DC+ power posts as shown. Mount only
one cable per post
4. Mount the breaker assembly to the cabinet wall using the
hardware provided.
Ref
P/N
Description
Pylon p/n label
B2 #3796
DC+ breaker cable
RED 400 mm
WI0CUS300001
B3 #3797
DC+ breaker cable
RED 780 mm
WI0PUS300001
P+ #2923 PCS DC+ power cable
-
1
2
3
4