8 ESS startup procedure
CAUTION! Powering the ESS requires a specific start-up procedure.
Please follow the steps below.
CAUTION! If the battery disconnect has been placed in the OFF
position at any time during operation, wait one minute before
returning to the ON position. Rapid cycling (less than one minute)
of the battery disconnect can cause damage to the pre-charge
circuit.
CAUTION! During the first start-up sequence after installation,
the battery modules may require a battery maintenance cycle to
balance the SOC. This maintenance cycle requires a grid
connection so that the PCS can be commanded to charge the
batteries. The PCS battery SOC alarm light will flash yellow if
maintenance and/or other battery faults are present. This
procedure may take from a few minutes to a few hours, depending
on the difference in battery module SOC.
Refer to the BMS face plate in figure 15 that applies to the battery model
supplied with the system.
1. Turn ON the BMS power switch to all battery modules in the
cabinet.
2. Press and hold the Start button on the master battery module for
0.5 seconds. The master battery is the lower-front module in the
battery cabinet. Wait for the battery module to initialize to the
normal/idle state. See also figure 10, module position 1 for
reference.
3. Turn ON the battery disconnect.
4. Turn ON the AC source disconnect and/or breaker at the electrical
panel.
8.1 System operation
The ESS is fully automated. The EMS will be programmed to
connect the system to the grid after AC and DC sources are
applied. The operating states can also be viewed on the PCS
display panel. For more details on system operation, refer to the
Owner’s Manual.
EMS
US3000C
1
2
3
Figure 19: ESS startup procedure.