Install Manual

25
13 Specifications
Table 1: PCS Electrical / Mechanical Ratings
Model
D
-
5 kW
Mode
Grid : Charging
Grid
: Discharging
Off Grid
Maximum DC Voltage
80 V DC
Operating DC Voltage Range
40 to 80 V DC
Operating DC Voltage Range
at 100% Output Power
40 to 80 V DC
Maximum DC Current
100 A
125 A
125 A
AC Power Factor*
0.8 lagging to 0.8 leading, adjustable
N/A
Operating Voltage Range (default)
105.6 to 132 V AC for L
1
-
N and L
2
-
N
N/A
Operating Voltage Range (with ride
-
through)
60.0 to 132 V AC for L
1
-
N and L
2
-
N
Operating Frequency Range (default)
59.3
60.5 Hz
N/A
Operating Frequency Range (with
ride
-
through)
50.0
66.0 Hz
N/A
Number of Phases
Split Phase
Nominal Output Voltage*
120 V AC for L
1
-
N and L
2
-
N or 240 V AC L
1
-
L
2
Normal Output Frequency*
60 Hz
Maximum Continuous Output Current
20.8 A for L
1
and L
2
Maximum Continuous Output Power (total) 5000 W
Maximum Allowed Overload Condition (as percentage of
maximum continuous current)
100% 100%
100
-
120 %
-
30 minutes
120-170 % - 5 seconds
Maximum Output Overcurrent Protection
60 A for AC Grid
,
60 A for AC Load
Maximum AC Short
-
circuit
Current
404 Apk
-
pk
(< 5 ms)
, 8.0 Arms
Maximum Synchronization In
-
rush Current
1.7 Arms
Protective Class (I, II, or III)
Class I
Over
-
Voltage Category (OVC I, II, III, or IV)
OVC III
Pollution Degree
3
Lightning protection
IEEE 62.41.2, location category B, low exposure
Normal Operation Temperature Range / Humidity
-
40 to +50 °C (limited by battery, see below)
Normal Operation Humidity
Max 95% (non
-
condensing)
Maximum Full Power Operating Ambient
40 °C
50 °C
Enclosure Rating
Type 3R
Dimensions
20.8”W x 30.8”H x 15.6”D (529 x 783 x 397 mm)
Weight
145 lbs (65 kg)
Default Trip Limits: UL1741 (IEEE 1547.1)
Low Volt Trip (adj.), Volts
Default
105.6
V AC (L
1
-
N or L
2
-
N)
N/A
Min/Max
0
105.6
V AC (L
1
-
N or L
2
-
N)
N/A
Low Volt Trip (adj.), time
Default
1257 cycles (21
Sec.)
N/A
Min/Max
1257
-
2997
cycles (
21
49.95
Sec.)
N/A
High Volt Trip (adj.), Volts
Default
132 V AC (L
1
-
N or L
2
-
N)
N/A
Min/Max
132
-
144
V AC (L
1
-
N or L
2
-
N)
N/A
High Volt Trip (adj.) time
Default
57 cycles
(0.95 Sec.)
N/A
Min/Max
57
-
777
cycles (0.95
12.95
N/A
Undervoltage: (Very Low) Trip Limit < 60 V AC (L
1
-N or L
2
-N) N/A
Undervoltage: (Very Low) Trip Time ≤ 117 cycles (1.95 Sec) N/A
Overvoltage: (Very High) Trip Limit > 144 V AC (L
1
-N or L
2
-N) N/A
Overvoltage: (Very High) Trip Time ≤ 10 cycles (0.16 Sec) N/A
Under Frequency
Trip Limits
(Adjustable)
Min
50.0
Hz
N/A
Default
58.5
Hz
N/A
Max
59.
0
Hz
N/A
Over Frequency
Trip Limits
(Adjustable)
Min
61.0
Hz
N/A
Default
61.2
Hz
N/A
Max
66.0
Hz
N/A
Frequency Trip Limit Accuracy
0.1 Hz
N/A
Frequency Trip Time Accuracy
0.1 Sec
N/A
Voltage Trip Limit Accuracy
2%
N/A
Voltage Trip Time Accuracy
0.043 Sec
N/A
Compliance
Safety
UL 1741SA, UL 1998, UL 9540