Install Manual
29
Table 9: SA11 Ramp rate settings.
SA11 Ramp Rates
Parameter Value for Rule 21 Value for Rule 14H
Output current rating for function [A] 20.8
Minimum normal ramp up rate [%Irated/sec] 1.0%
Maximum normal ramp up rate [%Irated/sec] 100.0%
Minimum output current [A] 0
Ramp rate accuracy [%Irated/sec] N/A
Minimum soft start ramp up rate [%Irated/sec] 0.1%
Maximum soft start ramp up rate [%Irated/sec] 100.0%
Default normal ramp up rate [%Irated/sec] 100.0% 100.0%
Default soft start ramp function status Enabled Enabled
Default soft start ramp up rate [%Irated/sec] 2.0% 0.33%
Table 10: SA12 Specified power factor settings.
SA12 Specified Power Factor
Parameter Value for Rule 21 Value for Rule 14H
Apparent power rating for function [VA] 5000
Output power rating for function [W] 5000
DC input voltage range with function enabled [V] 40.0 - 80.0
Nominal AC voltage [V] 120
AC voltage range with function enabled [V] 105.6 - 132.0
AC voltage accuracy [%Vnom or V] 1%, 1.2V
DC voltage measurement accuracy [V] 0.05
Active power range of function [W] 1000 - 5000 250 - 5000
Power Factor Accuracy 0.01
Power Factor settling time [sec] 5
Minimum inductive power factor -0.8
Minimum capacitive power factor 0.8
Mid inductive power factor -0.9
Mid capacitive power factor 0.9
Default function status Disabled Disabled
Power factor default -0.95 -0.95