Install Manual

31
Table 12: SA14 Frequency-Watt settings.
SA14 Frequency Watt
Parameter Value for Rule 21 Value for Rule 14H
Output power rating for function [W] 5000
AC frequency range with function enabled [Hz] 50.0 - 66.0
AC frequency measurement accuracy [Hz] 0.02
P(f) accuracy [%Prated or W] 2%, 100W
Settling time [sec] 3
Adjustment range of response time [s] 0.5 - 5.0
Adjustment range of the start of frequency droop [Hz] 59.964 - 63.0
Maximum slope of frequency droop [%Prated/Hz] 100.0%
Minimum slope of frequency droop [%Prated/Hz] 23.8%
Default function status Enabled Enabled
Default response time, ramp to 10% Prated [s] 0.5 0.5
Default start frequency [Hz] 60.2 60.036
Default slope of frequency droop [%Prated/Hz] 50.0% 33.0%
Default use of hysteresis (symmetric recovery) Enabled Enabled
Under-frequency response function status Enabled Disabled
Default under-frequency start [Hz] 59.964 59.964
Default slope of under-frequency droop [%Prated/Hz] 50.0% 33.0%
Table 13: SA15 Volt-Watt Settings.
SA15 Voltage Watt
Parameter Value for Rule 21 Value for Rule 14H
Output power rating for function [W] 5000
AC voltage range with function enabled [V] 120.0 - 132.0
Nominal AC voltage [V] 120
AC voltage accuracy [%Vnom or V] 1%, 1.2V
Output power accuracy [%Prated or W] 2%, 100W
Time accuracy [s] 2
Setting time [sec] 3
Adjustment range of the start of active power reduction [V] 122.4 – 130.8
Adjustment range of the stop of the curtailment function [V] 121.2 – 129.6
Maximum Slope of active power reduction [%Prated/V] 33.3%
Minimum slope of active power reduction [%Prated/V] 10.4%
Range of adjustment of a delay before return to normal operation
[sec]
1.0 – 60.0
Adjustment range of the rate of return to normal operation
[%Prated/sec]
10.0 - 100.0%
Default function status Disabled Disabled
Power duration reference Pre-disturbance Rated
Default response time, ramp to 10% Prated [s] 1 10
Default start voltage [V] 127.2 127.2
Default stop voltage [V] 126.0 127.2
Default active power slope [%Prated/V] 20.8% 33.3%
Default use of hysteresis (symmetric recovery) Disabled Enabled
Default delay before return to normal operation [s] 1 N/A
Default active power rate of return to normal operation [%Prated/s] 100 N/A