Submittal

1 Form No. V1.0_02.21
Specifications are subject to change without notice.
© 2021 Ferguson Enterprises LLC
www.durastar.com
12,000 BTU/H CEILING CASSETTE HEAT PUMP SYSTEM
Indoor Unit (IDU):
DRAC12F1A
Panel:
DRACPANA1A*
Outdoor Unit (ODU):
DRA1U12S1A
Wireless Remote
Control
PROJECT NAME
LOCATION
ARCHITECT
ENGINEER
CONTRACTOR
REFERENCE
SUBMITTED BY DATE
SUBMITTAL COVER SHEET
EFFICIENCY DATA
SEER 21.5
EER 14.0
HSPF 10.5
CAPACITIES
Cooling Capacity (BTU/hr)
Rated
1
12000
Minimum 3850
Maximum 13000
Heating Capacity (BTU/hr)
Rated
2
12000
Minimum 4000
Maximum 14890
OUTDOOR TEMPERATURE OPERATION
Cooling -13 °F - 122 °F
(-25 °C - 50 °C)
Heating -13 °F - 86 °F
(-25 °C - 30 °C)
ELECTRICAL DATA
Voltage/Phase/Frequency
208-230V, 1 Phase, 60 Hz
Voltage Range 187-253V
Recommended Breaker (Amps) 15
Minimum Circuit Ampacity (Amps) 12
Minimum Wire Size 16 AWG
Rated Current - Cooling (Amps)
1
3.9
Rated Current - Heating (Amps)
2
4.2
1
Measured at 95 °F.
2
Measured at 47 °F.
PRODUCT FEATURES
Wireless Remote Control with "Follow Me" Technology
Variable Speed Inverter Compressor
Auto Restart
Auto Changeover
24-hour Timer
Self Clean Function
*Panel sold separately