DRA5U48M1A Submittal

1 Form No. V1.0_02.21
Specifications are subject to change without notice.
© 2021 Ferguson Enterprises LLC
www.durastar.com
48,000 BTU/H MULTI-ZONE HEAT PUMP SYSTEM
Multi-Zone Outdoor Unit (ODU):
DRA5U48M1A
PROJECT NAME
LOCATION
ARCHITECT
ENGINEER
CONTRACTOR
REFERENCE
SUBMITTED BY DATE
SUBMITTAL COVER SHEET
EFFICIENCY DATA
DUCTLESS DUCTED
SEER 21.5 20.5
EER 11.6 10.1
HSPF 10.4 11.5
CAPACITIES
DUCTLESS DUCTED
Cooling Capacity
(BTU/hr)
Rated
1
48000 49000
Minimum 14500 19400
Maximum 53100 51000
Heating Capacity
(BTU/hr)
Rated
2
48000 50000
Minimum 14000 15500
Maximum 56900 56000
OUTDOOR TEMPERATURE OPERATION
Cooling -13 °F - 122 °F
(-25° C - 50° C)
Heating -13 °F - 86 °F
(-25° C - 30° C)
ELECTRICAL DATA
DUCTLESS DUCTED
Voltage/Phase/Frequency
208-230V, 1 Phase, 60 Hz
Voltage Range 187-253V
Recommended Breaker (Amps) 50
Minimum Circuit Ampacity (Amps) 35
Minimum Wire Size 16 AWG
Rated Current - Cooling (Amps)
1
16.7 21.1
Rated Current - Heating (Amps)
2
17.0 17.8
1
Measured at 95 °F.
2
Measured at 47 °F.
PRODUCT FEATURES
Variable Speed Inverter Compressor
Included Base Pan Heater
Auto Restart