Multi-Zone Outdoor Condenser Installation Manual

DURASTAR.COM
15
Note on refrigerant valve selection for indoor units
For DRA3U28M1A and DRA4U36M1A:
If installing a 24,000 BTU indoor unit, only connect the unit to the valve ports labeled "A" on the
outdoor unit.
For DRA5U48M1A:
If installing one 24,000 BTU indoor unit, only connect the unit to the valve ports labeled "A" on the
outdoor unit. If installing two 24,000 BTU indoor units, only connect the units to the valve ports
labeled "A" and "B" on the outdoor unit.
REFRIGERANT PIPING CONNECTIONS
REFRIGERANT PIPE LENGTH
The length of refrigerant piping will affect the performance and efficiency of the unit. Nominal
efficiency is tested with a pipe length of 25 feet (7.6 meters). A minimum pipe run of 10 feet (3
meters) is required to minimize vibration and excessive noise.
Refer to the table on page 13 for specifications on the maximum length and drop height of
refrigerant piping.
WARNING
When connecting refrigerant piping, do not let substances or moisture other than
specified refrigerant enter the unit or pipes. The presence of foreign materials will
lower the unit's capacity and can cause abnormally high pressure in the refrigeration
system. This can result in explosion and personal injury.
Note on master valves
For DRA3U28M1A, DRA4U36M1A, and DRA5U48M1A:
Initial startup
Once installation is complete and a vacuum is maintained on all applicable zones, open both
master valves. Then, starting with valve A, open all valves connected to an IDU to allow the
release of refrigerant into those zones. After all the refrigerant is released, both master valves
and all zone valves connected to an IDU must remain open for proper operation.
Refrigerant connecting pipe sizes
for indoor units
Indoor Unit capacity
(Btu/h)
Liquid Gas
9K 1/4” 3/8”
12K &18K 1/4” 1/2”
24K 3/8” 5/8”
A” and “B” valve ports.
DRA5U48M1A shown.
Master Valves