5.7 Anti-frost protection during winter
This protection can only be activated if the heat pump is in STAND-BY mode.
5.7.1 First anti-frost protection
If the filter pump is controlled by the heat pump (regardless of the value for parameter 9) and when the water
temperature lies between 2 and 4 °C and the air temperature is lower than 0 °C, the filter pump will be
automatically turned on to prevent the water from freezing in the piping. This protection is deactivated when the
temperature rises again.
5.7.2 Second anti-frost protection
If the water temperature drops even more, that is, below 2 °C (during long frost periods), the heat pump will
also start running to heat the water until its temperature approximates 3 °C. When this temperature is reached,
the heat pump will stop, but anti-frost protection will remain active until conditions change.