Instruction manual

EU heat pumps
21
Problem:
the heat pump works but stops after a short while
Observation:
the screen displays “OFF”
Possible cause
Solution
 Wrong setting of parameters
 Check the settings of the parameters and modify if
necessary
Problem:
the heat pump doesn’t stop
Observation:
the screen displays the temperature but no error codes
Possible cause
Solution
 Wrong setting of parameters
 Check the set parameters and adjust them if
necessary (settings just above the capacity of the
heat pump)
 Pressure switch out of order
 Check operation of the pressure switch by turning
off the filter pump and restarting it. If the heat
pump doesn’t react to this, the pressure switch
must be adjusted or replaced.
 Electrical failure
 Contact your installer
Problem:
water leak
Observation:
there’s an amount of water under the heat pump
Possible cause
Solution
 Condensation due to atmospheric humidity
 No action required
 Water leak
 Try to localize the leak and check for the presence
of chlorine in the water. If that is the case, the heat
pump must be temporarily replaced during repair.
Problem:
abnormal amount of ice formed on the evaporator
Observation:
the evaporator is for the most part covered in ice
Possible cause
Solution
 Insufficient air inflow
 Check the location of the heat pump and remove
any dirt that could be present on the evaporator
 High water temperature
 If the pool water is already quite hot (warmer than
29 °C), the probability of ice formation increases.
Lowering the set temperature is a possible option.
 Incorrect setting of automatic defrost control
 Check the settings of the defrosting function
together with your installer
 The 4-way valve is out of order
 Check the voltage in the electrical wiring to the 4-
way valve. If electric potential is measured,
replace the coil. If the problem persists, have the
heat pump checked by a refrigeration technician.
 Not enough refrigerant
 Have the heat pump checked by a refrigeration
technician.