Install Instructions
Stainless Horizontal (Fig.14)
1.  Cut opening in the wall.
2.  Add Trim Plates and Locking Clamp/
Band (if applicable) to nal pipe length 
before installing. Make sure anges 
are facing towards the wall. Use non-
hardening sealant where necessary. 
3.  After Exterior Trim Plate is mounted to 
wall, measure 3" from Exterior Plate and 
cut o female pipe end and deburr. Seal 
pipe to Exterior Plate. Slide Bird screen 
over cut pipe end and tighten clamp.
Vertical single pipe (Fig.15)
1.  Follow instructions for Vertical 
Concentric Termination on page 16.
2.  Attach Flashing to roof. (Fig.15)
•  Use a rubber boot ashing or 
similar, ensure an eective, leak-
proof seal is maintained.
•  Use BLACK UV protected pipe.
3.  Maintain 12 in. (305mm) min. clearance 
above highest anticipated snow level, 
max 24 in. (610mm) above roof.
MULTIPLE VENTS IN ONE CONDUIT 
Fig.16
Multiple PolyPro vent systems may be 
installed within one conduit, including 
but not limited to masonry or factory-built 
chimneys. Listed 2"-4" components must 
11
CUT LINE
  THROUGH HOLE SIZING
4PPS: 4.125"   5PPS: 5.25"
6PPS: 6.125"   8PPS: 8.00"
EXTERIOR TRIM PLATE
INTERIOR TRIM PLATE
PP PIPE
INITIAL
FINAL
BIRD 
SCREEN
CLAMP
FLANGES
Figure 14
BLACK
UV PROTECTED PIPE
RUBBER FLASHING
Figure 15- Vertical Pipe Termination
BIRD GUARD
be used, the conduit cannot be in use for 
another appliance, and the conduit (if pre-
existing) must be inspected and deemed 
sound.
Upper supports may be eld supplied and 
listed. The listing requires: Min thickness of 24 
ga (0.020") SS, no larger than 18" Dia or 18" 
max length rectangle, 4 vent runs max per 
support. The listing requires clearance holes 
no larger than 5 1/8" Dia, with spacing 1 3/4" 
apart.
RIGID BLACK 
UV PROTECTED 
POLYPRO
GASKET 
PLATE 
STAINLESS 
RELINE 
HANGER 
BRACKET
RIGID 
POLYPRO
STAINLESS
UPPER 
SUPPORT 
PLATE
GASKET PLATE 
/ HANGER 
MOUNT 
HARDWARE
FLANGE
Figure 16
CLEARANCE 
HOLE 
1.75" MAT'L 
SPACE MIN