Install Instructions
4
LISTING
Listed to ULC S636 
Rated Class IIA, IIB, and IIC vent system
maximum temperature 230°F (110 °C)
maximum positive pressure 15 in-w.c. 
Massachusetts Plumbers Board, 
# G1-0811-42
APPLICATION
ANSI Category II and IV gas-burning 
appliances with a maximum positive 
pressure of 15in w.c. and maximum ue gas 
temperature of 230°F (110°C, ULC-S636-Class 
IIC). 
Appliances specically tested and listed to 
use DuraVent PolyPro Venting.
PERMITS
Check with your local Building Ocial, Fire 
Ocial, or other authority having jurisdiction 
(AHJ) regarding permits, restrictions, and 
installation inspections in your area.
GENERAL INSTALLATION NOTES
Read these instructions before beginning. 
You must use only authorized DuraVent 
PolyPro vent parts, or other parts specically 
authorized in these instructions and/or listed 
by the appliance manufacturer in order to 
maintain a safe, approved system.
•  Do not mix parts or try to match with 
other products or use improvised 
solutions. 
•  Do not install damaged or modied 
parts. 
•  Use soapy water to lubricate gaskets.
•  Never use petroleum base lubricants.
If these directions and those of the appliance 
manufacturer dier, follow the more 
conservative requirements. If you have any 
questions, contact either your dealer or 
DuraVent directly. A venting system must 
not be routed into, through, or within any 
other vent, such as an existing masonry or 
factory-built chimney ue, unless that vent 
or chimney is not being used to vent another 
appliance and is only used as a conduit for 
the gas-vent system. Plastic venting systems 
shall not pass through re rated separations 
without approved restopping. 
PolyPro Single-Wall attains Flame Spread / 
Smoke Developed ratings of <25 / <50 (per 
UL-723, ASTM E-84 and ULC-S102) when 
used in conjunction with the below noted 
materials:
•  3M Fire Barrier Plenum Wrap 5A+
•  Unifrax FyreWrap 0.5 Plenum Insulation
•  Knauf Insulation- Atmosphere Duct 
Wrap with ECOSE
•  Alternate equivalent listed product
Always follow the particular installation 
instructions from the insulation wrap 
manufacturer, in addition to those for the 
PolyPro vent system. The venting system 
shall be securely supported using suitable 
hangers installed after the pipe has been 
properly wrapped. Hardware must not 
deform or damage the vent or wrap.
Table 1
Clearance to Combustibles
  VENT PIPE ORIENTATION
Single Wall Vertical Horizontal
Up to 190°F 0" 0"
Up to 230°F 0" ¼" (6mm) all around
Concentric
Up to 230°F 0" 0"
The vent system must be compliant in 
accordance with local code requirements 
and appropriate National Codes: In 
the US: NFPA 54 / ANSI Z223.1 National 
Fuel Gas Code or the International Fuel 
Gas Code. In Canada: CAN/CGA-B149.1 
Natural Gas Installation Code or CAN/CGA-
149.2 Propane Installation Code.
IMPORTANT