Install Instructions
8
Figure 5
APPLIANCE 
OUTLET
POLYPRO 
VENT PIPE
TIGHTEN CLAMPS ON 
RUBBER COUPLER 
ADAPTER OR FERNCO 
STYLE ADAPTER TO 
SECURE VENT 
PIPE TO APPLIANCE
APPLIANCE CONNECTION: 2" - 4"
1.  If the appliance has a PVC/CPVC female 
outlet, use the Appliance Adapter/ PVC 
Adapter and Clamp. (Fig.4) 
2.  If the appliance has a PVC/CPVC Male 
outlet use a matching PVC/CPVC 
coupling to convert to a female outlet.
3.  If the appliance outlet has a rubber 
boot or Fernco-style appliance adapter, 
then the PolyPro vent pipe may attach 
directly to the appliance (Fig.5).
4.  If the appliance has a FasNSeal outlet 
use the FasNSeal to PolyPro adapter.
Figure 4
POLYPRO PIPE
APPLIANCE 
ADAPTER CLAMP
APPLIANCE ADAPTER/
PVC ADAPTER
APPLIANCE 
EXHAUST OUTLET 
OR PVC UNION
APPLIANCE 
INSTALLATION
1.  Pipe lengths may be cut to length 
(Fig.6). If the Locking Tab is removed 
use the new Locking Clamp (Fig.3b PPS-
LC) or alternative clamp ( Fig.4 PPS-PAC 
/ PPS-LBC) for the connection.
•  Cut square (not at an angle) to the 
end of the pipe. 
•  Remove burrs before assembly.
2.  Check with appliance manufacturer for 
any restrictions or limits on vent length, 
number of elbows, etc.
3.  The slope of the vent pipe must be at 
least 1.8° (3/8" rise per ft run, 31mm 
per meter) back to the appliance. 
Ensure there are no dips in the system 
where condensate can collect. (Fig.7)
Figure 6
MARK
CUT WITH 
HACKSAW
DEBURR
Figure 7
12"
3/8" 
MIN
1/4"  5/8"
7.5mm  15mm
TO APPLIANCE
PP Pipe sections must be disengaged 
1/4"-5/8" per joint (to allow for expansion) 
and sloped 1.8°(3/8"per ft) back to the 
appliance per Fig.7 for proper condensate 
flow.
IMPORTANT