Install Instructions
14
INSTALLATION
1.  Certain Concentric PolyPro vent pipe may 
be cut to length. On the vent sections 
where this is allowed, a label specifying 
"Can be cut. This end only" will be placed 
on the male end. If the vent section does 
not have this label then DO NOT cut the 
pipe.      
Follow these steps to cut:
•  Mark where along the outer sleeve 
where you intend to cut. Make sure 
the mark is square (not at an angle) 
to the end of the pipe.
•  Use a hack saw with a metal cutting 
blade and cut along the mark 
through only the outer sleeve.
•  Mark the inner sleeve so it is 1/4in 
(7mm) to 1/2in (14mm) longer than 
the outer. Cut along the mark.
•  Remove burrs on the inner and 
outer sleeves before assembly.
2.  Check with appliance manufacturer for 
any restrictions or limits on vent length, 
number of elbows, etc.
3.  All vent pipes must have a minimum 
slope of at least 1.8° (3/8in rise per ft 
run, 31mm rise per meter run) back to 
the appliance. Ensure there are no dips 
in the system where condensate can 
collect. (Fig.20)
4.  The venting system shall be securely 
supported using suitable hangers. 
DuraVent hardware is recommended 
however eld supplied support hardware, 
such as all-thread or plumbers tape, 
approved by the AHJ is acceptable. 
Hardware must be xed to a rigid surface 
such as a wall, stud, or framing, and must 
not deform or damage the vent (Fig. 20 
and 21). Make sure the load of the vent 
system is not supported by the appliance. 
•  Vertical vent sections must be 
supported with Wallstraps every 
6.5ft (2m) or less. (Fig.21)
3/8IN
31MM
MIN
12IN
1M
MIN
TO APPLIANCE
Figure 20
Figure 21
4IN
100MM
MAX
3.25FT
1M MAX
6IN
150MM MAX
6.5FT
2M
MAX
Figure 22
4IN 100MM
MAX
4IN 100MM
MAX